Start-up
Setting of application program parameters is not needed. Parameter 21.09 START
INTRL FUNC is set to OFF2 STOP at the factory.
Use
How to activate the emergency stop
Push the emergency stop push-button.
How to deactivate the emergency stop
WARNING! Ensure that it is safe to apply input voltage:
• It is safe to start the motor.
• All cabinet doors are closed.
Step
What to do
1.
Turn the emergency stop push-button clockwise until the button
releases.
2.
Press the blue fault reset button on the cabinet door:
SUPPLY TRIPPED
RESET
3.
ACS800-07: Turn the manual
operating switch on the front
door to position S for 2
seconds.
0
ACS800-17/37: The manual
operating switch on the front
door in position I.
I
0
S
Category 0 emergency stop for ACS800-07/17/37 (+Q951, n×R8i)
The emergency stop activates and the button
locks in the "ON" position.
What happens
The emergency stop deactivates.
The blue light goes out.
ACS800-07: The line contactor or air
circuit breaker closes. The drive and
motor become live.
ACS800-17/37: The drive is ready to
start.
I