Wiring

One emergency stop push-button is installed on the cabinet door and wired to the
drive at the factory. Wire the additional emergency stop push-buttons to terminal
block X8 (terminals 3, 4, 5 and 6) inside the drive cabinet. See the circuit diagram
delivered with the drive.

Start-up

Digital I/O Extension Module RDIO-01 is configured as an emergency stop signal
interface at the factory. In case optional module slots 1 and 2 on the RMIO board (or
RDCU control unit) are reserved, the digital I/O extension module is placed on the
I/O Module Adapter AIMA-01.
User settings are listed below.
Set the ramp time by parameter 22.07 EM STOP RAMP TIME according to the application
requirements.
If the ramp time is changed, check that relays K22 and K23 have slightly longer delay times.
If the AIMA-01 module adapter is in use, check that its node address is the same as in the circuit
diagram delivered with the drive. See AIMA-01 I/O Module Adapter User's Manual [3AFE64661442
(English)].

Use

How to activate the emergency stop

Push the emergency stop push-button.
Category 1 emergency stop for ACS800-07/17/37 (+Q952, R6i, R7i, n×R8i)
The emergency stop activates and the button
locks in the "ON" position.