Huawei FusionDC1000A Quick Manual page 10

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:

Advertisement

Note:
1. The concrete platform must support a maximum weight of 15000 kg. The recommended seismic acceleration is 3 g.
The concrete platform strength is calculated based on the contact area (see the contact area of a single base 1720
cm2/ on the ground). For details, consider the engineering margin.
2. Each base has eight mounting holes. Only four holes need to be installed. The four holes outside the base are
preferred. If the external holes meet the reinforcement of the foundation, use the internal holes.
3. Ensure that the direction of the single base is consistent with that in the drawing.
Ground
Single-capacity base
340
260
400
Single-capacity base
Concrete platform
1000
Name
Drawing No.
Qty
Unit
Single-capacity
base
DKBA40703508
4
PCS
T-shaped bolt
DKBA80473086
4
PCS
Expansion bolt DKBA04802828_M16×150_S
16
PCS
>=10,058
加湿补排水口
底部进线口
281
600
1,000
1,000
1,351
550
6,254
7,354
混凝土支撑平台
No.S002 Site Space and Pre-fab. Module Installation Pos
(Single-capacity Base Scenario)
Concrete platform