Siemens Sinamics S120 Manual page 59

Power units, booksize c/d type format
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

C-type
Current carrying capacity
DC link busbars
Reinforced DC link busbars
24 V DC busbars
Unit rating
3)
based on I
(600 V DC; 4 kHz)
rated
based on I
H
Typical power loss
See also Power losses of the components (Page 116)
Max. pulse frequency
Without derating
With derating
Max. ambient temperature
without derating
with derating
Sound pressure level
Cooling method
Cooling air requirement
Max. permissible heat sink temperature
Weight
Values applicable to a DC link voltage of 720 V DC at an output voltage of 400 V 3 AC
1)
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V and is adjusted to the parame-
2)
terized line voltage
Rated power of a typical standard induction motor at 400 V 3 AC.
3)
Table 3- 8
Technical data of Double Motor Modules in booksize D-type format (2 x 3 A to 2 x 18 A)
D-type
Output current (at 600 V DC)
Rated current (l
)
n
Base-load current (I
)
H
Intermittent duty current (I
Peak current (l
)
max
Output voltage
Output frequency
DC link current
1)
Rated current I
d rated
DC link voltage
DC link capacitance
Overvoltage trip
Undervoltage trip
2)
Electronics power supply
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1
6SL3120-
A
AC
A
AC
) 40%
A
s6
AC
A
AC
V
AC
Hz
A
DC
V
DC
μF
V
DC
V
DC
V
DC
Motor Modules in booksize C/D-type format
3.2 Motor Modules with internal air cooling
6SL3120-
2TE21-8AC.
A
100
DC
A
150
DC
A
20
DC
kW
2 x 9.7
kW
2 x 8.2
W
281
kHz
4
kHz
16
°C
40
°C
55
dB(A)
< 60
Internal fan
m
/h
56
3
°C
91
kg
7.7
2TE13-
2TE15-
0AD.
0AD.
2 x 3
2 x 5
2 x 2.6
2 x 4.3
2 x 4
2 x 6.7
2 x 9
2 x 15
0 ... 0.717 x DC link voltage
(0 ... 480 V at 670 V DC)
7.2
12
220
220
24 (20.4 ... 28.8)
2TE21-
2TE21-
0AD.
8AD.
2 x 9
2 x 18
2 x 7.7
2 x 15.3
2 x 12
2 x 24
2 x 27
2 x 54
0 ... 550
22
43
510 ... 720
220
705
820 ± 2 %
380 ± 2 %
59

Advertisement

Table of Contents
loading

Table of Contents