4.1 Motor connector
Table 4- 1
Conductor and stripped insulation lengths as a function of the cable cross-section, data in mm and (inch)
a
U
55 +2/-3
(2.17 +0.08/-0.12)
V
W
PE
64 +2/-3
(2.52 +0.08/-0.12)
BR-
73 ±5
(2.87 ±0.20)
BR+
79 ±5
(3.11 ±0.20)
Note
Adherence to conductor and stripped insulation lengths
It is important to cut the conductors and strip the insulation to the specified lengths.
Individual conductors might otherwise sustain damage.
Furthermore, failure to adhere to the conductor and stripped insulation lengths makes it
impossible to create a contact between the shield and the shield support.
Note
Electrical connection of cables with cross-section of 10 mm
Preassembled MOTION-CONNECT power cables must be used when cables with a cross-
section of 10 mm
Note
Cables for UL applications
For UL applications, only 60/75 °C copper cables may be used.
72
1.5 mm
(AWG 16)
2
b
12 ±0.5
(0.47 ±0.02)
12 ±0.5
(0.47 ±0.02)
12 ±0.5
(0.47 ±0.02)
12 ±0.5
(0.47 ±0.02)
(AWG 8) are required.
2
2.5 / 4 / 6 mm
(AWG 14 / AWG 12 / AWG 10)
2
a
55 +2/-3
(2.17 +0.08/-0.12)
62 +2/-3
(2.44 +0.08/-0.12)
73 ±5
(2.87 ±0.20)
79 ±5
(3.11 ±0.20)
(AWG 8)
2
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1
b
12 ±0.5
(0.47 ±0.02)
12 ±0.5
(0.47 ±0.02)
12 ±0.5
(0.47 ±0.02)
12 ±0.5
(0.47 ±0.02)