NOTICE
Damage in operation due to insufficiently rated DC link busbars
The DC link busbars of the individual components have different current ratings. If the
current flowing through a DC link busbar is higher than the current specified for the busbar,
the component will heat up and may sustain damage as a result of overheating.
• When designing a drive line-up, make sure that the current ratings of the individual
6.5.2.2
Installation
Always connect the lower DC link busbars first, then the upper DC link busbars and finally
the 24 V busbars.
Required tools:
● Slot-head screwdriver (1 x 5.5) for releasing the protective cover
● Screwdriver Torx T20 for the DC link screws
● Pliers for removing the side covers of the DC link protective covers
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1
components are adequate for the application, or reduce the load current if necessary.
Alternatively, you can use reinforced DC link busbars (Page 80).
Cabinet design
6.5 Electrical connection
95