Associations Between Alarms and Dry
Table C-1 Associations between alarms and dry contacts
Port Type
Dry contact input
Dry contact output
The default setting
(closed: alarm;
open: normal) can
be modified.
Issue 05 (2020-04-07)
Silk Screen
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
ALM1
ALM2
ALM3
ALM4
ALM5
ALM6
ALM7
ALM8
Copyright © Huawei Technologies Co., Ltd.
C Associations Between Alarms and Dry Contacts on the
Contacts on the UIM
Associated Alarm
Dry contact input 1
Dry contact input 2
Dry contact input 3
Dry contact input 4
Dry contact input 5
Dry contact input 6
AC Failure/Long Mains Failure
DC Ultra Overvoltage/DC Overvoltage/DC
Ultra Undervoltage/DC Undervoltage
Rectifier Fault/Rectifier Protection/Rectifier
Communication Failure/Rectifier Fault
(Redundant)/Rectifier Fault
(Non-redundant)/Multi-Rectifier Fault/All
Rectifiers Fail to Communicate
AC SPD Fault/DC SPD Fault
Load Fuse Break/Battery Fuse Break
Reserved
Reserved
Reserved
UIM
79