C Associations Between Alarms And Dry Contacts On The Uim - Huawei TP48200A-HX09A2 User Manual

Outdoor power system
Hide thumbs Also See for TP48200A-HX09A2:
Table of Contents

Advertisement

TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual
C
Associations between Alarms and Dry
Table C-1 Associations between alarms and dry contacts
Port Type
Dry contact input
Dry contact output
Issue 02 (2019-02-26)
Silk Screen
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
ALM1
ALM2
ALM3
ALM4
ALM5
Copyright © Huawei Technologies Co., Ltd.
C Associations between Alarms and Dry Contacts on the
Contacts on the UIM
Associated Alarm
Dry contact input 1
Dry contact input 2
Dry contact input 3
Dry contact input 4
Dry contact input 5
Dry contact input 6
Reports alarms for mains faults.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for DC output overvoltage or
undervoltage.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for module faults.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for AC surge protective device
(SPD) faults or DC SPD faults.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for battery fuse blown, load fuse
blown, and loop disconnection.
Default mode (Close: alarm; Open: normal) can
be modified as required.
UIM
90

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tbc300a-tca2

Table of Contents