Water Alarm; Smoke Alarm; Rect Fault; Rect Protection - Huawei TP48200A-HX09A2 User Manual

Outdoor power system
Hide thumbs Also See for TP48200A-HX09A2:
Table of Contents

Advertisement

TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual

4.2.17 Water Alarm

Possible Causes
Measures
1.
2.

4.2.18 Smoke Alarm

Possible Causes
Measures
1.
2.

4.2.19 Rect Fault

Possible Causes
Measures
1.
2.

4.2.20 Rect Protection

Possible Causes
Issue 02 (2019-02-26)
This alarm is generated only for the power system that has a water sensor installed.
There is water inside the cabinet.
The water sensor is faulty.
Check whether there is water inside the cabinet. If so, remove the water with dry cotton
or other tools and then locate and rectify the fault.
Check whether the water sensor is faulty. If the water sensor is faulty, replace it.
This alarm is generated only for the power system that has a smoke sensor installed.
There is smoke inside the cabinet.
The smoke sensor is faulty.
Check whether there is smoke inside the cabinet. If so, disconnect the power supply from
the cabinet, handle the fault, and then restart the system and clear the alarm on the SMU.
Check whether the smoke sensor is faulty. If the smoke sensor is faulty, replace it.
Rectifier connections are loose.
A rectifier is faulty.
Check the Fault indicator on the rectifier panel. If it is steady red, remove the rectifier,
and then reinstall it after the indicator turns off.
If the alarm persists, replace the rectifier.
The rectifier input voltage is too high.
The rectifier input voltage is too low.
The ambient temperature is too high.
Copyright © Huawei Technologies Co., Ltd.