Item

4.2 Rectifying Common Faults

4.2.1 AC Failure

Possible Causes
Measures
1.
2.
3.

4.2.2 AC Over Volt

Possible Causes
Measures
1.
2.

4.2.3 AC Under Volt

Possible Causes
Issue 02 (2019-02-26)
Maintenance Task
Check
Whether
the equipment
room.
The AC input power cable is faulty.
The AC input circuit breaker is OFF.
The power grid is faulty.
Check whether the AC input cable is loose. If so, secure the AC input cable.
Check whether the AC input circuit breaker is OFF. If so, handle the fault which caused
the AC input circuit breaker to turn OFF and then switch on the circuit breaker.
Check whether the AC input voltage is lower than 50 V AC. If so, handle the power grid
fault.
The AC overvoltage alarm threshold is incorrectly set on the SMU.
The power grid is faulty.
Check whether the AC overvoltage alarm threshold is correctly set. If not, set the
threshold to the correct value.
Check whether the AC input voltage exceeds the AC overvoltage alarm threshold (280 V
AC by default). If so, handle the AC input fault.
The AC undervoltage alarm threshold is incorrectly set on the SMU.
The power grid is faulty.
Copyright © Huawei Technologies Co., Ltd.
Check
Repair When
Method
wrench.
bar in the
equipment
room is loose or
damaged.
4 Maintenance
Measures
44