Electromagnetic Compatibility Specifications; Cabinet Specifications - Huawei TP48200A-HX09A2 User Manual

Outdoor power system
Hide thumbs Also See for TP48200A-HX09A2:
Table of Contents

Advertisement

TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual
A.3 Electromagnetic Compatibility Specifications
Table A-3 Electromagnetic compatibility (EMC) specifications
Item
Electromagnetic
interference
(EMI)
Electromagnetic
susceptibility
(EMS)
A.4 Cabinet Specifications
Table A-4 Cabinet specifications
Item
Dimensions (H x W x D)
Base (H x W x D)
Cabinet weight
Protection level
Installation mode
Issue 02 (2019-02-26)
Specifications
Conducted emission (CE)
Radiated emission (RE)
Harmonic
Fluctuation and flick
Electrostatic discharge (ESD)
Electrical fast transient (EFT)
Radiated susceptibility (RS)
Conducted susceptibility (CS)
Surge susceptibility
Specifications
900 mm x 650 mm x 650 mm (excluding the base and
protruding part)
100 mm x 650 mm x 650 mm
TP48200A-HX09A2: ≤ 75 kg (without rectifiers)
TBC300A-TCA2: ≤ 56 kg (without batteries)
IP55
TP48200A-HX09A2: installed on a floor, installed against a
wall, combined with a battery cabinet, or stacked on a battery
cabinet
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
Class A, EN300386
Class A, EN300386
IEC 61000-3-12
IEC 61000-3-11
Contact discharge: 6 kV (criterion B);
air discharge: 8 kV (criterion B)
EN61000-4-4
Signal port: ± 1 kV (criterion B); AC
power port: ± 2 kV (criterion B); DC
power port: 2 kV (criterion B)
Field strength: 10 V/m (criterion A)
Signal port: 3 V (criterion A); power
port: 10 V (criterion A)
EN61000-4-5
AC and DC power ports: differential
mode: ± 2 kV (criterion B); common
mode: ± 4 kV (criterion B). Signal
port: differential mode: 0.5 kV
(criterion B); common mode: 1 kV
(criterion B)
86