Huawei TP48200A-HX09A2 User Manual page 13

Outdoor power system
Hide thumbs Also See for TP48200A-HX09A2:
Table of Contents

Advertisement

TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual
Item
Heater
Temperature control unit
(TCU)
Cabinet
PDU
Rectifier
Site monitoring unit (SMU)
User interface module
(UIM)
Sensor
Lamp
Battery
Maximum output power
Issue 02 (2019-02-26)
TP48200A-HX09A2
None
Equipment compartment:
heat exchanger
Equal to or greater than 8 U
high space for customer
equipment
AC PDU: AC input
circuit breaker, AC
output circuit breaker,
and maintenance socket
DC PDU: battery low
voltage disconnection
(BLVD), load low
voltage disconnection
(LLVD), and battery
branch
A maximum of four
R4850G1s or R4850N1s can
be configured.
One SMU02B
One UIM02C
Mandatory: one battery
temperature sensor, one
door status sensor, and
one ambient temperature
sensor
Optional: one smoke
sensor, one ambient
temperature and
humidity sensor, and one
water sensor
Optional: one lamp
N/A
12 kW
Copyright © Huawei Technologies Co., Ltd.
1 Overview
TBC300A-TCA2
TEC with a heating function
Battery compartment: TEC
N/A
N/A
N/A
N/A
N/A
One door status sensor and
one battery temperature
sensor
N/A
Battery compartment of two
layers: two front-access
battery strings (12 V/100
Ah) can be configured.
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tbc300a-tca2