Associations between Alarms and Dry
Table A-1 Associations between alarms and dry contacts
Port Type
Dry contact input
Dry contact output
Issue 01 (2013-10-25)
A Associations between Alarms and Dry Contacts on the
Silk Screen
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
ALM1
ALM2
ALM3
ALM4
ALM5
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Contacts on the UIM
Associated Alarm
Dry contact input 1
Dry contact input 2
Dry contact input 3
Dry contact input 4
Dry contact input 5
Dry contact input 6
Reports alarms for mains faults.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for DC output overvoltage or
undervoltage.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for module faults.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for AC surge protective device
(SPD) faults or DC SPD faults.
Default mode (Close: alarm; Open: normal) can
be modified as required.
Reports alarms for battery fuse blown, load fuse
blown, and loop disconnection.
Default mode (Close: alarm; Open: normal) can
be modified as required.