Precautions For Replacement Of Parameter; Conversion From Anscpu To Qcpu - Mitsubishi Electric MELSEC Q Series Handbook

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

7
REPLACEMENT OF PROGRAM

7.3 Precautions for Replacement of Parameter

7.3.1 Conversion from AnSCPU to QCPU

This section explains the parameter conversion upon replacement of the AnSCPU programs with the
QCPU.
<Compatibility>
: Common item between AnSCPU and QCPU, that can be converted directly.
: Item that requires re-setting after the conversion, since the functions/specifications are partially
different
: Item to be deleted, since there is no common item between the AnSCPU and QCPU.
Confirm the parameters after the conversion, and correct/re-set as required.
Name
Sequence program capacity
Microcomputer program capacity
Comment capacity
File register capacity
WDT setting
Operation mode when these is an error
Annunciator display mode
RUN - PAUSE contact
Output mode at STOP to RUN
Data communications request batch
processing
Interrupt counter setting
I/O assignment
Number of device points
Latch relay L
Data register D
Link relay B
Link register W
Low-speed timer
High-speed timer
Extension low-speed timer
Extension high-speed timer
Retentive timer
Extension retentive timer
Counter
Extension counter
MELSECNET (II), /B
MELSECNET/10 (H)
MELSECNET/MINI
7
- 27
Compat-
ibility
No need to care about the program capacity.
No microcomputer program is available.
Not required, since comments can be created for all devices.
Resetting is required since the specifications are different.
This becomes default (200ms).
This becomes default (All stop).
No compatible function is available.
Re-setting is required.
This becomes default (Output before STOP).
Use COM instructions, or set the service processing setting in the PLC parameter.
Re-setting is required.
Reviewing is required for the base unit with other than 8 slots.
This resets to default.
M and L are different devices.
"L" on the program is converted to "L".
Converted as one device.
Reviewing is required, since all the range from lowest device No. to highest device No. is
included in the latch range.
Converted as one device.
Reviewing is required, since all range from lowest device No. to highest device No. is
included in the latch range.
Converted as one device.
Reviewing is required, since the latch range covers all range from lowest device No. to
highest device No.
Parameters are deleted, since the Q series CPU is not compatible with the MELSECNET
(II), /B.
For A2USCPU, converted to the MELSCECNET/10 mode.
Parameter re-setting is required for the AnS(H)CPU.
Parameters are deleted, since the QCPU is not compatible with the MELSECNET/MINI.
Remarks