3.2.4 Comparison of interrupt module specifications

(1) Specifications comparison between A1SI61 and QI60
Specifications
Number of interrupt input
points
Isolation method
Rated input voltage
Rated input current
Operating voltage range
Maximum number of
simultaneous input points
On voltage
Off voltage
Input resistance
Off  on
Response
time
On  off
Interrupt condition setting
Common terminal
arrangement
Operation indication
External connection
system
Applicable wire size
Applicable solderless
terminal
Number of occupied
I/O points
Current consumption
External dimensions
Weight
*1
Check the specifications of the sensor or switch to be connected to the QI60.
A1SI61
16 points
Photocoupler
12/24VDC
Approx. 4mA (12VDC)
Approx. 8mA (24VDC)
10.2 to 26.4VDC
Simultaneously on (100%)
9VDC or more/3mA or more
4VDC or less/1mA or less
Approx. 2.7k
0.2ms or less
0.2ms or less
In increments of 4 points
16 points/common
(common terminal: TB9, TB18)
On indication (LED)
20-point terminal block connector
(M3.57 screws)
2
0.75 to 1.5mm
1.25-3.5, 1.25-YS3A, 2-3.5, 2-YS3A,
V1.25-3.5, V1.25-YS3A, V2-S3,
V2-YS3A
32 points (I/O assignment: special
32 points)
0.057A (TYP, all points on)
130(H)34.5(W)93.6(D)mm
0.20kg
: Compatible,
QI60
16 points
Photocoupler
24VDC
Approx. 6mA
20.4 to 28.8VDC
(ripple ratio within 5%)
Simultaneously on (100%)
19VDC or more/4.0mA or more
11VDC or less/1.7mA or less
Approx. 3.9k
0.1ms/0.2ms/0.4ms/0.6ms/1ms or
less
(Configure the setting in the PLC
parameter dialog box.)
0.2ms is set by default.
0.1ms/0.2ms/0.4ms/0.6ms/1ms or
less
(Configure the setting in the PLC
parameter dialog box.)
0.2ms is set by default.
In increments of 1 point
16 points/common
(common terminal: TB17)
On indication (LED)
18-point terminal block
(M36 screws)
2
Core: 0.3 to 0.75mm
(outside diameter: 2.8mm or less)
R1.25-3
(Sleeved solderless terminal cannot
be used.)
16 points (I/O assignment: Interrupt)
0.06A (TYP. all points on)
98(H)27.4(W)90(D)mm
0.20kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
12VDC is not applicable.
The rated input current is
*1
reduced.
12VDC is not applicable.
*1
12VDC is not applicable.
*1
12VDC is not applicable.
The input resistance is
*1
increased.
Set the input response time of
parameter to the default value
(0.2ms).
Wiring change is required.
The number of occupied I/O
points differs.
Wiring space is narrower.
3