Mitsubishi Electric MELSEC Q Series Handbook page 125

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
REPLACEMENT OF I/O MODULE
(8) Specifications comparison between A1SY40P and QY40P
Specifications
Number of output points
Isolation method
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at off
Maximum voltage drop
at on
Off  on
Response
On  off
time
Surge suppressor
Fuse
Common terminal
arrangement
Operation indication
Protection function
External
Voltage
power
supply
Current
External connection
system
Applicable wire size
Applicable solderless
terminal
Current consumption
External dimensions
Weight
A1SY40P
16 points
Photocoupler
12/24VDC
10.2-30VDC
(peak voltage 30VDC)
0.1A/point, 0.8A/common
0.7A 10ms or less
0.1mA or less
0.1VDC (typ.) 0.1A
0.2VDC (MAX.) 0.1A
1ms or less
1ms or less
(rated load, resistance load)
Zener diode
None
8 points/common
(common terminal: TB10, TB20)
On indication (LED)
Available
(overheat protection function,
overload protection function)
• The overheat protection function is
activated in increments of 1 point.
• The overload protection function is
activated in increments of 1 point.
12/24VDC
(10.2 to 30VDC)
11mA
(typ. 24VDC for each common)
20-point terminal block connector
(M3.57 screws)
2
0.75 to 1.5mm
R1.25-3.5, R2-3.5,
RAV1.25-3.5, RAV2-3.5
0.079A (typ. all points on)
130(H)34.5(W)93.6(D)mm
0.13kg
: Compatible,
QY40P
16 points
Photocoupler
12/24VDC
10.2-28.8VDC
0.1A/point,1.6A/common
0.7A 10ms or less
0.1mA or less
0.1VDC (typ.) 0.1A
0.2VDC (MAX.) 0.1A
1ms or less
1ms or less
(rated load, resistance load)
Zener diode
None
16 points/common
(common terminal: TB18)
On indication (LED)
Available
(overheat protection function,
overload protection function)
• The overheat protection function is
activated in increments of 1 point.
• The overload protection function is
activated in increments of 1 point.
12-24VDC
(10.2 to 28.8VDC
ripple ratio within 5%)
MAX.10mA (24VDC)
(all points on)
18-point terminal block
(M36 screws)
2
Core: 0.3 to 0.75mm
(outside diameter: 2.8mm or less)
R1.25-3
(Sleeved solderless terminal cannot
be used.)
0.065A (typ. all points on)
98(H)27.4(W)90(D)mm
0.16kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
Voltage exceeding 28.8VDC is
not applicable.
-
As the common is changed from
2 commons to 1 common, wiring
with a different voltage for each
common is not possible.
Voltage exceeding 28.8VDC is
not applicable.
Wiring change is required.
Wiring space is narrower.
The weight is increased.
3
- 72

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-ans/qnas

Table of Contents