Mitsubishi Electric MELSEC Q Series Handbook page 127

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
REPLACEMENT OF I/O MODULE
(10)Specifications comparison between A1SY41P and QY41P
Specifications
Number of output points
Isolation method
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at off
Maximum voltage drop
at on
Off  on
Response
On  off
time
Surge suppressor
Fuse
Common terminal
arrangement
Operation indication
Protection function
External
Voltage
power
supply
Current
External connection
system
Applicable wire size
Current consumption
External dimensions
Weight
A1SY41P
32 points
Photocoupler
12/24VDC
10.2 to 30VDC
(peak voltage 30VDC)
0.1A/point 2A/common
0.7A 10ms or less
0.1mA or less
0.1VDC (typ.) 0.1A
0.2VDC (MAX.) 0.1A
1ms or less
1ms or less
(rated load, resistance load)
Zener diode
None
32 points/common
(common terminal: A1, A2)
On indication (LED)
Available
(overheat protection function,
overload protection function)
• The overheat protection function is
activated in increments of 1 point.
• The overload protection function is
activated in increments of 1 point.
12/24VDC
(10.2 to 30VDC)
12mA
(typ. 24VDC for each common)
40-pin connector (accessory)
2
0.3mm
0.141A (typ. all points on)
130(H)34.5(W)93.6(D)mm
0.15kg
: Compatible,
QY41P
32 points
Photocoupler
12-24VDC
10.2 to 28.8VDC
0.1A/point 2A/common
0.7A 10ms or less
0.1mA or less
0.1VDC (typ.) 0.1A
0.2VDC (MAX.) 0.1A
1ms or less
1ms or less
(rated load, resistance load)
Zener diode
None
32 points/common
(common terminal: A01, A02)
On indication (LED)
Available
(overheat protection function,
overload protection function)
• The overheat protection function is
activated in increments of 1 point.
• The overload protection function is
activated in increments of 1 point.
12-24VDC
(10.2 to 28.8VDC
ripple ratio within 5%)
20mA (24VDC)
40-pin connector (sold separately)
2
0.3mm
(A6CON1, A6CON4)
0.105A (typ. all points on)
98(H)27.4(W)90(D)mm
0.15kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
Voltage exceeding 28.8VDC is
not applicable.
-
Voltage exceeding 28.8VDC is
not applicable.
The current value is increased.
Existing external wiring can be
used.
3
- 74

Advertisement