ABB Relion REF615R Manual page 28

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

Section 4
1x Registers
DPU2000R
register
DPU 2000R description
addr.
10002
Breaker Status (52a = 0 52b= 1 CB Open)
(52b)
10003
Enable Reclose Function Asserted (43a)
10004
Enable Phase Over current Protection for all
Phase elements except 50P-3 (PH3)
10005
Enable Ground Over current Protection for all
Ground elements except 50N-3 (GRD)
10006
Spring Charging Contact Function Enabled
(SCC)
10007
Single Shot Reclosing Enabled (79S)
10008
Multiple Shot Reclosing Enabled (79M)
10009
Trip Coil Monitoring Enabled (TCM)
10010
Enable 50P-1 and 50N-1 (50-1)
10011
Enable 50P-2 and 50N-2 (50-2)
10012
Enable 50P-3 and 50N-3 (50-3)
10013
Enable Alternate 1 Settings (ALT1)
10014
Enable Alternate 2 Settings (ALT2)
10015
Initiate Event Capture 1 (ECI1)
10016
Initiate Event Capture 2 (ECI2)
10017
Waveform Capture Initiate (WCI)
10018
Enable Zone Sequence Coordination (ZSC)
10019
Initiate Trip Output (OPEN)
10020
Initiate Close Output (CLOSE)
10021
Enable Negative Sequence Time Over current
Function (46)
10022
Enable Positive Sequence Directionally
Controlled Phase Time Over current Function
(67P-1)
10023
Enable Negative Sequence Directionally
Controlled Phase Time Over current Function
(67N)
10024
User Logical Input 1 Element Energized (ULI1)
10025
User Logical Input 2 Element Energized (ULI2)
10026
User Logical Input 3 Element Energized (ULI3)
10027
User Logical Input 4 Element Energized (ULI4)
10028
User Logical Input 5 Element Energized (ULI5)
10029
User Logical Input 6 Element Energized (ULI6)
10030
User Logical Input 7 Element Energized (ULI7)
10031
User Logical Input 8 Element Energized (ULI8)
10032
User Logical Input 9 Element Energized (ULI9)
22
REF615R
register
IEC 61850 path
addr.
10002
CTRL.CBCSWI1.PosOpn.stVal
10003
*LD0.DARREC1.AROn.stVal
10006
LD0.SSCBR1.InSprCha.stVal
10008
LD0.DARREC1.InReClsOn.stVal
DR.RDRE1.RcdTrg.stVal
10018
LD0.DARREC1.ProCrd.stVal
10019
CTRL.CBCSWI1.OpOpn.general
10020
CTRL.CBCSWI1.OpCls.general
10021
LD0.NSPTOC1.Mod.blockIn
1MRS240173-IB B
Comments on REF615R
Modbus points mapping
Apparatus open position
Auto reclosing allowed
See Section 7.2.1 for
example or explanation
See Section 7.2.2 for
example or explanation
N/A in REF615R
N/A in REF615R
See Section 7.2.3 for
example or explanation
See Section 7.2.4 for
example or explanation
See Section 7.2.5 for
example or explanation
See Section 7.2.6 for
example or explanation
See Section 7.2.7 for
example or explanation
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
DPU2000R Modbus Point List Mitigation Manual
REF615R

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dpu2000r

Table of Contents