ABB Relion REF615R Manual page 49

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

1MRS240173-IB B
DPU2000R
DPU 2000R
register
description
addr.
41156
Password
character 3 & 4
41157
Spare
41158
Change initiate
input mask
41159:14
Control button 6
(C6)
41159:13
Toggle SCADA
Redi
41159:12
Reset energy
meters
41159:11
Reset relay
status
41159:10
Reset Min/Max
demands
41159:9
Reset Alarms
41159:8
Reset LED
Targets
41159:7
Control button 5
(C5)
41159:6
Control button 4
(C4)
41159:5
Close Initiate
(Independent of
43A)
41159:4
Control button 3
(C3)
41159:3
Control button 2
(C2)
41159:2
Control button 1
(C1)
REF615R
DPU2000R Modbus Point List Mitigation Manual
REF615R
register
IEC 61850 path
addr.
41156
41157
41158
41187:10
LD0.SPCGGIO3.SPCSO6.Oper.ctlVal
41187:11
41162:10
LD0.SPEMMTR1.SupDmdRs.Oper.ctlVal
41162:12
LD0.PEMMTR1.SupDmdRs.Oper.ctlVal
41162:6
LD0.LLN0.MtrRecRs.Oper.ctlVal
41162:8
LD0.LLN0.LEDRs1.Oper.ctlVal
41162:9
LD0.LLN0.LEDRs2.Oper.ctlVal
41187:8
LD0.SPCGGIO3.SPCSO5.Oper.ctlVal
41187:9
41187:6
LD0.SPCGGIO3.SPCSO4.Oper.ctlVal
41187:7
41157:1
CTRL.CBCSWI1.Pos.Oper.ctlVal
41157:2
41157:3
41157:5
41187:4
LD0.SPCGGIO3.SPCSO3.Oper.ctlVal
41187:5
41187:2
LD0.SPCGGIO3.SPCSO2.Oper.ctlVal
41187:3
41187:0
LD0.SPCGGIO3.SPCSO1.Oper.ctlVal
41187:1
Section 5
4x Registers
Comments on REF615R Modbus points
mapping
In REF615R, it is mapped for the password
2 for the control structure 1.
In REF615R, this register is mapped to
control open or close the circuit breaker.
Please see the rows below.
In REF615R, it is mapped for the
confirmation register for the control structure
1.
Control button 6 (C6) set
Control button 6 (C6) reset
N/A in REF615R.
Reset energy meters single phase
Reset energy meters in 3 phase
N/A. In REF615R, status automatically
resets for the Modbus client who reads the
status register.
Control button 5 (C5) set
Control button 5 (C5) reset
Control button 4 (C4) set
Control button 4 (C4) reset
"Close" command in
SBO-with-enhanced-security mode. (Relay
needs to be set at Remote mode at first).
"Cancel" command in
SBO-with-enhanced-security mode. Send
this command within 15 seconds delay after
sending the "Close" command to cancel the
"Close" command.
"Select" command in
SBO-with-enhanced-security mode. Send
this command within 15 seconds delay after
sending the "Close" command to confirm the
"Close" command.
"Close" command in
direct-with-normal-security mode. (Relay
needs to be set at Remote mode at first).
Control button 3 (C3) set
Control button 3 (C3) reset
Control button 2 (C2) set
Control button 2 (C2) reset
Control button 1 (C1) set
Control button 1 (C1) reset
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dpu2000r

Table of Contents