Table 21. Mitigation Of Modbus Mapping For Operation Records; Table 22. One Example Of Modbus Event Record Value - ABB Relion REF615R Manual

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

Section 5
4x Registers
DPU2000R
register
DPU 2000R description
addr.
N/A
41537
Data Control 1=First record;
2=Next record; 3=Oldest
Unreported record
41538
Year
41539
Month
41540
Day
41541
Hours
41542
Minutes
41543
Seconds
41544
Hundredths of Seconds
41545
Message #
41546
Value
41547
Operation Number
N/A
N/A
48
Table 21:
Mitigation of Modbus mapping for operation records
REF615R
Scale
register
addr.
41536
1
41537
1
41538
1
41539
1
41540
1
41541
1
41542
1
41543
1
41544
1
41545
1
41546
1
41547
41548
41549
Different from decoding the operation number to find out event type as in DPR2000R,
REF615R reads the Modbus addresses associated with the event.
In one case, for example, the operation record has the following readings as shown in
Table 22.
Table 22:
One example of Modbus event record value
Event records addresses
41546
41547
41548
41549
User needs to check "Feeder Protection and Control REF615R Modbus Point List
Manual", document ID: 1MRS240052-IB to find out 10513 is mapped to IEC61850 path
of "CTRL.CBCSWI1.PosOpn.stVal" and its description is "52-1 Apparatus open
position", and understands value of 1 means "breaker open" as status value is set as 1.
By default, some Modbus registers do not generate event upon value changes. To make
them generate events, user can use PCM600 / CMT tool to enable event from "rising edge"
or "both edge" of the signal's status change. On the other hand, user can disable generate
default event from PCM6000 / CMT by simply checking off the event enable bit as shown
in Figure 6.
Scale
Comments on REF615R Modbus points mapping
Number of Events to Read per polling, read max.10 events at
the same time, not available in DPU2000R
1
Data Control 1=First record; 2=Next record; 3=Oldest
Unreported record
1
Year
1
Month
1
Day
1
Hours
1
Minutes
1
Seconds
1
Hundredths of seconds
1
Sequence number after device powers up, it does not count fault
records saved before power up.
1
Value (high word)
1
Value (low word)
1
Area of the Register on which the event happened (0 = coil; 1=
input, 4 = 4x)
1
Register address on which the event happened
values
meaning
0
Higher word value is 0
1
Lower word value is 1
1
Register area is 1, it is a 1x register
513
Register address is 513
DPU2000R Modbus Point List Mitigation Manual
1MRS240173-IB B
REF615R

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dpu2000r

Table of Contents