Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

Section 5
4x Registers
5.1.2
DPU2000R
register
DPU 2000R description
addr.
40129:0
Self test status
40129:1
contact input changed
40129:2
local settings changed
40129:3
remote edit disable
40129:4
Alternate 1 Settings Active
40129:5
Alternate 2 Settings Active
40129:6
New Fault Recorded
40129:7
Control Power Cycled
40129:8
New Operation recorded
40129:9
New peak demand value
40129:10
New minimum demand value
40129:11
Momentary changes
30
c. If the primary PT rating is 20KV, to get the primary voltage reading in KV, fill in five
into the "Min In" column. It is because the original signal's scale factor is already 100.
Thus, 20 (1/5*100 = 20) will be UDR's value's effective scaling. (It eventually
multiplies voltage per unit reading by 20).
Figure 4:
UDR divisor scaling factor to convert a voltage reading from pu to
primary KV
If the original signal is mapped into 32 bit, the UDR shall keep it as 32 bit
register by leaving the next register as "Empty Register".

System Status/Configuration Block

REF615R keeps as many status registers in DPU2000R as possible for the purpose of self
diagnostics. The mappings for some registers without direct IEC 61850 paths, such as
"heart beat", are implemented by software. Some registers in DPU2000R mapped for its
obsolete hardware or device configurations are reserved as blanks.
Table 11:
Mitigations of Modbus system status/configuration block
REF615R
Scale
register addr.
40129:0
40129:1
40129:3
40129:4
40129:5
40129:6
40129:7
40129:8
40129:9
40129:10
40129:11
Scale
IEC 61850 path
DPU2000R Modbus Point List Mitigation Manual
1MRS240173-IB B
Comments on REF615R
Modbus points mapping
Self test status
contact input changed
N/A in REF615R
remote edit disable
Alternate 1 Settings
Active
Alternate 2 Settings
Active
New Fault Recorded
Control Power Cycled
New Operation recorded
New peak demand value
New minimum demand
value
Momentary changes
REF615R