Table 15. Mitigation Of Modbus Mappings For Minimum Demand Current/Real, Reactive Power Values And Time Stamps Block - ABB Relion REF615R Manual

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

1MRS240173-IB B
DPU2000R
register
DPU2000R description
addr.
40641
Minimum Demand Current-A
40642
Minimum Demand Current-A Year,
Month
40643
Minimum Demand Current-A Day,
Hour
40644
Minimum Demand Current-A Minute
40645
Minimum Demand Current-B
40646
Minimum Demand Current-B Year,
Month
40647
Minimum Demand Current-B Day,
Hour
40648
Minimum Demand Current-B Minute
40649
Minimum Demand Current-C
40650
Minimum Demand Current-C Year,
Month
40651
Minimum Demand Current-C Day,
Hour
40652
Minimum Demand Current-C Minute
40653
Minimum Demand Current-N
40654
Minimum Demand Current-N Year,
Month
40655
Minimum Demand Current-N Day,
Hour
40656
Minimum Demand Current-N Minute
40657
Minimum Demand KWatts-A
40659
Minimum Demand KWatts-A Year,
Month
40660
Minimum Demand KWatts-A Day,
Hour
40661
Minimum Demand KWatts-A Minute
40662
Minimum Demand KWatts-B
40664
Minimum Demand KWatts-B Year,
Month
40665
Minimum Demand KWatts-B Day,
Hour
40666
Minimum Demand KWatts-B Minute
40667
Minimum Demand KWatts-C
40669
Minimum Demand KWatts-C Year,
Month
40670
Minimum Demand KWatts-C Day,
Hour
REF615R
DPU2000R Modbus Point List Mitigation Manual
Table 15:
Mitigation of Modbus mappings for minimum demand current/real, reactive power values and time
stamps block
REF615R
Scale
register
addr.
1
40641
40642
40643
40644
1
40645
40646
40647
40648
1
40649
40650
40651
40652
1
40653
40654
40655
40656
1
40657
40659
40660
40661
1
40662
40664
40665
40666
1
40667
40669
40670
Scale
IEC61850 path
100
LD0.CMSTA1.MinAmpsA.mag.f
LD0.CMSTA1.MinAmpsA.t
100
LD0.CMSTA1.MinAmpsB.mag.f
LD0.CMSTA1.MinAmpsB.t
100
LD0.CMSTA1.MinAmpsC.mag.f
LD0.CMSTA1.MinAmpsC.t
100
LD0.RESCMSTA1.MinAmps.mag.f
LD0.RESCMSTA1.MinAmps.t
1
LD0.SPEMSTA1.MinWPhsA.mag.f
LD0.SPEMSTA1.MinWPhsA.t
1
LD0.SPEMSTA1.MinWPhsB.mag.f
LD0.SPEMSTA1.MinWPhsB.t
1
LD0.SPEMSTA1.MinWPhsC.mag.f
LD0.SPEMSTA1.MinWPhsC.t
Section 5
4x Registers
Comments on
REF615R
Modbus points
mapping
reading per unit
value by default
Year, Month
Day, Hour
Minute
reading per unit
value by default
Year, Month
Day, Hour
Minute
reading per unit
value by default
Year, Month
Day, Hour
Minute
reading per unit
value by default
Year, Month
Day, Hour
Minute
Year, Month
Day, Hour
Minute
Year, Month
Day, Hour
Minute
Year, Month
Day, Hour
39