Download Print this page

LG 5BPU0-02D Engineering Product Data Book page 21

Air-to-water heat pump / split type r410a/50hz

Advertisement

THERMA V
Split Type
6. Hydraulic Performance
6.1 Water Pump Capacity
Water volume and pump capacity
The water pump is BLDC, so it may be required to change default water pump speed in case of noise by waterflow.
In most case, however, it is strongly recommended to set speed as Maximum.
Notice
Water pump speed : To secure enough water flow rate, do not set water pump speed as "Min."
It can lead unexpected flow rate error CH14.
 AHNW16606A3, AHNW16809A3
16.00
14.00
12.00
10.00
8.00
6.00
4.00
2.00
0.00
0
Performance test based on standard ISO 9906 with pre-pressure 2.0bar and liquid temperature 20°C.
WARNING
Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.
12
Min. flow
1500
1000
10
20
30
Pumping Capacity, Q (ℓ/min)
MAX. (RPM)
3500
3000
2500
2000
40
50
60
Hydro Box Unit
Pump model : PY-122NDDD3
70
80
90
100