Air-to-water heat pump / split type r410a/50hz

Advertisement

THERMA V
Split Type
2. Specifications
Power Supply
Operation Range
(Outdoor Tempera-
ture)
Compressor
Refrigerant
Refrigerant Oil
Heat Exchanger
Fan
Fan Motor
Sound Power Level
Piping Connections
Piping Length
Piping Level Difference
Dimensions
Weight
Wiring Connections
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions
and values are normally higher in actual operation.
4. Performances are based on the following conditions :
• Cooling : Inlet/Outlet Water Temp. 23°C/18°C, Outdoor Air Temp. 35°CDB / 24°CWB
• Heating : Inlet/Outlet Water Temp. 30°C/35°C, Outdoor Air Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
5. This product contains Fluorinated greenhouse gases.
6. Sound Performances are based on the following conditions.
• Sound Power Level : Measured according to EN14825.
• Sound Pressure Level : Calculated value according to distance of sound power.
8
Outdoor Units
Cooling
Min. ~ Max.
Heating
Min. ~ Max.
Domestic Hot
Min. ~ Max.
Water
Type
Model
Diplacement
Capacity
Motor Type
Motor Output
Rated
Type
GWP
(Global Warming Potential)
Precharged Amount
t-CO2 eq.
Chargeless-Pipe Length
Additional Charging Volume
Control
Type
Charged Volume
Quantity
Row
Specification
Column
s
Fins per Inch
Type
Air Flow Rate
Rated
Type
Output
Heating
Rated
Type
Liquid
Outer Dia.
Type
Gas
Outer Dia.
Standard
Max.
Outdoor Unit
Max.
~ Indoor Unit
Unit
W x H x D
Packed Unit
W x H x D
Unit
Packed Unit
Power Supply Cable
(Included Earth)
AHUW096A3 [HU091 U43]
V, Ø, Hz
220-240 / 1 / 50
°C DB
5 ~ 48
°C DB
-20 ~ 35
°C DB
-
Hermetic Motor
Model x No.
GJT240MAA x 1
cm³/Rev.
24
kW
7.41
-
BLDC
W x No.
2,137 x 1
-
R410A
-
2,087.5
g
1,800
-
3.76
m
7.5
g/m
40
-
Electronic Expansion Valve
-
FVC68D
cc x No.
570 x 1
EA
1
EA
2
EA
38
EA
14
-
Propeller
m³/min x No.
58 x 1
-
BLDC
W x No.
124 x 1
dB(A)
65
-
Flare
mm(inch)
Ø 9.52 (3/8)
-
Flare
mm(inch)
Ø 15.88 (5/8)
m
7.5
m
50
m
30
mm
950 x 834 x 330
mm
1,065 x 918 x 461
kg
59.0
kg
65.0
No. x mm²
3 x 4.0(H07RN-F)
AHUW126A3 [HU121 U33]
220-240 / 1 / 50
-
Hermetic Motor
GPT442MAA x 1
4,000 x 1
Electronic Expansion Valve
1,300 x 1
Propeller
Ø 9.52 (3/8)
Ø 15.88 (5/8)
950 x 1,380 x 330
1,140 x 1,462 x 461
3 x 6.0 (H07RN-F)
Outdoor unit
5 ~ 48
-20 ~ 35
-
44.2
13.92
BLDC
R410A
2,087.5
2,300
4.80
7.5
40
FVC68D
2
2
32
14
55 x 2
BLDC
124 x 2
66
Flare
Flare
7.5
50
30
94.0
107.0