LG 5BPU0-02D Engineering Product Data Book page 83

Air-to-water heat pump / split type r410a/50hz

Advertisement

THERMA V
Split Type
3. Installation Space
3.1 Clearance around outdoor units
• Ensure that the space around the back is
or more more than 300 mm on the
opposite to the PCB side and secure 600
mm space near the compressor and PCB
side of the air conditioner for service.
• Install the unit so that its discharge port
faces to the wall of the building. Keep a
distance 500mm or more between the unit
and the wall surface.
• Supposing the wind direction during the
operation season of the air conditioner,
install the unit so that the discharge port is
set at right angle to the wind direction.
4
300 mm or more
300 mm or more
Outdoor unit is representative. Actual appearance of outdoor unit
may be different but clearances will stay the same.
500
Air inlet grille
Turn the air outlet side toward the build-
ing's wall, fence or windbreak screen.
Outdoor unit is representative. Actual appearance of outdoor unit may be
different but clearances will stay the same.
Design and installation
300 mm
or more
300 mm
100 mm
100 mm
F e
or more
or more
or more
n c e
o b
s t a
o r
c l e
s
600 mm or more
(Service space)
700 mm
or more
Strong
wind
Strong
wind
Blown
air
Set the outlet side at a right angle
to the direction of the wind.