Product version: V8.30
Table 14: Ambient test
Description
Cold test
• Operation
• Storage
Dry heat test
• Operation
• Storage
Wet heat test
• Fixed status
• Loop
Table 15: Electro-magnetic compatibility test
Description
100kHz and 1MHz burst disturbance
test
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency interference tests
• Transmission, common mode
• Radiated, amplitude-modulated
Fast transient disturbance tests:
• Communication port
• Other ports
20
Type test
16 hours at -10ºC
16 hours at -25ºC
16 hours at +55ºC
16 hours at +70ºC
144 hours at +40ºC, humidity 93%
6 loops at +25...+55ºC, humidity 93-
95%
Type test value
2.5kV
1kV
8kV
15kV
10V(EMF),f=150kHz...80MHz
20V/m(RMS),f=80...1000MHz
and f=1.4...2.7GHz
4kV
4kV
Issued: May 2017
Reference standard
IEC 60068-2-1/ANSI
C37.90-2006
IEC 60068-2-2/ANSI
C37.90-2006
IEC 60068-2-78
IEC 60068-2-30
Reference standard
IEC 60255-4-18
IEC 60255-22-1, level 3
IEC61000-4-2:2008
IEC 60255-22-2, level 4
IEC 61000-4-6
IEC 60255-22-6, level 3
IEC 61000-4-3
IEC 60255-22-3, level 3
IEC 60255-22-4, level A
4CAE000359