Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30
Table 20: Parameters for disturbance recording and fault locating
Name
Phase overcurrent
Negative-sequence
overcurrent
Residual overcurrent
Phase overvoltage
Positive-sequence
overvoltage
Negative-sequence
overvoltage
Residual overvoltage
Phase undervoltage
Positive-sequence
undervoltage
Delta phase voltage
Delta residual voltage
Delta phase current
Delta residual current
Variation current
Over frequency
Low frequency
Rate-of-change frequency
Harmonic overvoltage
Binary signal
Fault Locating
ABB
Value (range)
0.1...20A
0.05...20A
0.05...20A
50...150V
50...150V
0.5...30V
0.5...200V
10...120V
10...120V
0.5...30V
0.5...30V
0.05...10A
0.05...10A
0.05...0.2%
50...55Hz
45...50Hz
0.05...1Hz/s
0.5...30V
Last for ≥ 2ms after binary signal
shift, trigger recording
-
Accuracy
Settings ≥ 10%In, accuracy: ±10%
Settings ≥ 10%In, accuracy: ±10%
Settings ≥ 10%In, accuracy: ±10%
±5%
±5%
Settings ≥ 3%Un, accuracy: ±5%
Settings ≥ 3%Un, accuracy: ±5%
±5%
±5%
Settings ≥ 5%Un, accuracy: ±10%
Settings ≥ 5%Un, accuracy: ±10%
Settings ≥ 10%In, accuracy: ±20%
Settings ≥ 10%In, accuracy: ±20%
±10%
±0.01
±0.01
±10%
Settings ≥ 10%Un, accuracy: ±5%
≤1ms
Outlet fault ≤ 2kM, others ≤ 5%
4CAE000359
Issued: May 2017
Revision: -
23