Typical Configurations; Key System Technical Specifications - Huawei FusionModule1000A20 Product Description

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One Data
Center
Product Description (380 V)

2.2 Typical Configurations

Table 2-2 Typical configurations
Category
Structural
system
Power supply
and distribution
system
Cooling system
Monitoring
system
Fire
extingui
shing
system

2.3 Key System Technical Specifications

Table 2-3 Key technical specifications
Item
System BOM number
Power
Power input
supply
and
distribu
Issue 01 (2019-10-31)
System Components
There is no raised floor or CT cabinets (user-supplied). The
supported CT cabinet dimensions (H x W x D) are 2200 mm x 600
mm x 800 mm, 2200 mm x 600 mm x 600 mm, and 2200 mm x 600
mm x 300 mm.
Cables and terminals for connecting the AC/DC power system to
CT cabinets are not configured.
PDF (MCCB input and ATS input), AC/DC power system
(TP48400B-N20B3 and TP48600B-N20B1 and TP481200B-N20B1),
and battery (150 Ah and 190 Ah and 1000 Ah)
Intelligent heat exchanger (3 kW and 5 kW), Fresh air integrated unit
(13.5 kW)
ECC800, DC power module, smart ETH gateway, ETH converter,
camera, SD card, T/H sensor, smoke sensor, access actuator,
single-door magnetic lock, exit button, IC card reader, and IC card
Manu
Emergency light, exit indicator, and hand-held fire extinguisher
al fire
(purchased locally)
exting
uishin
g
CE
Photoelectric smoke detector, heat detector, fire alarm bell, fire alarm
autom
horn/strobe, emergency light, exit indicator, extinguishant control
atic
panel, external fire alarm horn/strobe, emergency shutdown button, gas
fire
release indicator, electrical actuator, pneumatic switch, nozzle, fire
exting
cylinder, and ASD
uishin
g
(optio
nal)
Specifications
21262910
21262910-001
One 160 A
Two 250 A
input,
inputs,
three-phase
three-phase
four-wire+PE,
four-wire+PE,
Copyright © Huawei Technologies Co., Ltd.
2 Typical Application Scenarios and Typical
21262910-002
21262910-003
One 160 A
Two 250 A
input,
inputs,
three-phase
three-phase
four-wire+PE,
four-wire+PE,
Configuration
21262911
Two 250 A
inputs,
three-phase
four-wire +
7