3.3 Cooling System

3.3.1 Overview

The cooling system (8 kW and 16 kW) uses an intelligent heat exchanger that is embedded in
a wall of a pre-fab. module. The intelligent heat exchanger supplies cooled air through the
bottom of the intelligent heat exchanger to the far end of the intelligent heat exchanger.
Heated air then returns to the air return vent at the upper-middle part of the intelligent heat
exchanger. The indoor and outdoor heat exchangers are integrated and installed in a reserved
opening in the pre-fab. module. The outdoor heat exchanger does not need to be separately
installed.
When the outdoor temperature is suitable, the heat exchanger uses the heat pipe for heat
exchange. Therefore, the indoor equipment can be cooled without starting the compressor, so
as to save energy.
If the customer's actual load is lower than 25% of the planned total load, the humidity in the
data center may be too high. This is not a quality issue. You are advised to add a dehumidifier
in the data center.
Issue 01 (2019-10-31)
Vendor and
Battery
Model
Voltage
Shuangdeng IV
12 V
6-FMX-150B
Shuangdeng IV
12 V
6-FMX-200
Shuangdeng-G
2 V
FM-1000&240
20845
Copyright © Huawei Technologies Co., Ltd.
3 System Architecture
Dimensions
Weight
(H x W x D)
48 kg
550 mm x 110
mm x 310 mm
58 kg
559 mm x 125
mm x 315 mm
1392 kg
1350 mm x 394
mm x 1724 mm
34