Product Description (380 V)
Item
AC power
distribution
DC power
distribution
R4850G2
rectifier
Issue 01 (2019-10-31)
Cabling mode
Maintenance mode
IP rating
Input mode
Input voltage
Input capacity
Output voltage
Battery route
BLVD route
LLVD route
Surge protection
Efficiency
Output power
Dimensions (H x
W x D)
Weight
Copyright © Huawei Technologies Co., Ltd.
Specifications
Routed in and out from the top
Maintained from the front and located along a wall
with a clearance of at least 100 mm
IP20
220/380 V AC three-phase four-wire
85–300 V AC (L-N); rated voltage: 220 V AC
1 x 63 A/3P
–42 V DC to –58 V DC. The default output is –53.5
V DC.
4 x 125 A/2P
Standard: four 1-pole 63 A circuit breakers, two
1-pole 16 A circuit breakers, and two 1-pole 10 A
circuit breakers
Standard: two 1-pole 100A circuit breakers, two
1-pole 63 A circuit breakers, and four 1-pole 32 A
circuit breakers
AC surge protection: nominal lightning strike
discharge current 20 kA (8/20 µs), maximum
lightning strike discharge current 40 kA (8/20
µs)
DC surge protection: 10 kA in differential
mode, 20 kA in common mode, 8/20 µs
≥ 95% (230 V AC, 30%–100% load)
3000 W (176–300 V AC)
1250 W (linear derating at 85–175 V AC)
40.8 mm x 105 mm x 281 mm
< 2 kg
3 System Architecture
29

Advertisement

Table of Contents
loading

Table of Contents