Connection Of External Test - Beko BEKOMAT 16 CO Original Installation And Operation Manual

Table of Contents

Advertisement

Original installation and operation manual

7.2.3 Connection of external TEST

The BEKOMAT
has an option for the connection of an external TEST button. This enables condensate to be discharged
®
via remote control. If the external contact is closed, the solenoid valve opens like after pressing the TEST button on the
top cover and the BEKOMAT
Illustration
discharges condensate.
®
6 mm (0.23")
60 mm (2.36")
4
5
6
J
8
Normally Open (NO)
Common (CO)
Normally Closed (NC)
±24V
+24 VDC (0 V)
±24V
0 V (+24 VDC)
Description / explanation
1. Prepare the external TEST button cable.
If the potential free contact is to be connected
in addition to the external TEST button, a 4/5-
wire cable must be used for the connection
(depending on the application).
2. Take the guard plate [8] out of the left-hand cable
gland.
3. Slide the components of the cable gland [4, 5, 6] over
the cable [J] and insert the cable into the top cover.
4. Connect the cable of the external TEST button to the
control PCB in accordance with the terminal diagram.
BEKOMAT
16 CO
®
31 | 60