Operating Environment Specifications - Huawei FusionDC1000A Manual

Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)

5.2.2 Operating Environment Specifications

Operating Environment
Table 5-2 Operating environment
Item
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Outdoor temperature
Protection level
Issue 01 (2021-04-20)
The throttling device uses a miniature controller to control the operation of
the step motor, thereby changing the pass-through area of the EEV to
regulate the flow of refrigerant.
Check valve
Effectively prevents gas or liquid backflow.
Dryer filter
The filter dryer absorbs water from the refrigerant pipes and filters out the
foreign matter, which reduces component damage rates and improves
operating efficiency and reliability.
Sight glass
Users can observe the refrigerant flow and gas-liquid content through the
sight glass to realize easy maintenance and system optimization.
Electric heater
The positive temperature coefficient (PTC) electric heater features quick start,
large heating capacity, and even heat dissipation. It has multiple protection
mechanisms to ensure the safe and stable running of the equipment.
Humidifier
Controls the humidity in an equipment room.
Water pump
Drives the drainage.
Display
The LCD is a 7-inch color touchscreen that allows for query, setting,
monitoring, and maintenance.
Specifications
18–45°C
20%–80% RH
–40°C to +70°C
5%–95% RH (non-condensing)
● Work with NetCol500-A040MS1E0: –20°C to +45°C
● Work with NetCol500-A040MS1E0: –20°C to +55°C
● Work with NetCol500-A040MS1E0 (with a low temperature
component): –40°C to +45°C
● Outdoor unit: IPX5
Copyright © Huawei Technologies Co., Ltd.
5 Cooling System
54