Mitsubishi Electric MELSEC iQ-R Series Introduction Manual page 36

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Creating the recording setting
Use GX Works3 to configure the recording setting of the camera recorder module.
For details on the recording setting screen, refer to the following.
MELSEC iQ-R System Recorder User's Manual (Application)
There are two recording methods: "File Saving Trigger Only" and "Recording Startup Trigger + File Saving Trigger". The
following shows the setting example with the recording method using only the file saving trigger for recording data from 10
seconds before to 5 seconds after the device M0 turns on.
Setting item
Recording Setting
Operating procedure
1.
Add a new recording setting.
[Navigation] window  [Parameter]  [Recording Setting]  Right-click  [New]
*1 A new setting can also be created from the recording menu.
4 PROGRAMMABLE CONTROLLER SETTINGS
35
4.3 Recording Setting
Description
Configure the settings required for recording.
■Settings
• Recording Method: File Saving Trigger Only
• Specify the Devices/Labels in the Program in a Batch: Select
• Device: M0
• Saving Path Setting: SD memory card
• Video Data Receiving Target Setting: Select all
*1
Click here to configure
the recording setting.
Click here.

Advertisement

Table of Contents
loading

Table of Contents