Pre-fab.
Monitoring
Data
Device Code
Module
Device
Type
AIO
Collector_ECC800
FE
52271874
AIO
Collector_ECC800
FE
50100888
AIO
Collector_ECC800
FE
52273211
AIO
Collector_ECC800
FE
52273213
AIO
Collector_ECC800
FE
52273213
AIO
Collector_ECC800
FE
52273211
AIO
Collector_ECC800
FE
02290837
AIO
Collector_ECC800
FE
02290837
AIO
Collector_ECC800
RS485
02310RKM
Dry
AIO
Collector_ECC800
33010007
contact
Dry
AIO
Collector_ECC800
33010007
contact
Dry
AIO
Collector_ECC800
contact
Dry
52250103
AIO
Collector_ECC800
contact
Dry
AIO
Collector_ECC800
contact
Dry
AIO
Collector_ECC800
33010347
contact
Dry
AIO
Collector_ECC800
/
contact
Dry
AIO
Collector_ECC800
/
contact
Dry
AIO
Collector_ECC800
/
contact
Dry
AIO
Collector_ECC800
contact
Dry
AIO
Collector_ECC800
/
contact
Dry
AIO
Collector_ECC800
contact
Device Name
Device Model
Device IP Address
Access Actuator
UT-H101
/
WiFi Converter
ECC5EMSWF00
/
NetCol5000-
Air Conditioner-A1
/
A025H40E2
NetCol5000-
Air Conditioner-B1
/
A025H4WE2
NetCol5000-
Air Conditioner-C1
/
A025H4WE2
NetCol5000-
Air Conditioner-D1
/
A025H40E2
UPS-1
UPS5000-E
/
UPS-2
UPS5000-E
/
AI/DI Module-1
EN1MMEEM02A
/
Door Status Sensor-1
/
/
Door Status Sensor-2
/
/
FAULT RELAY
/
FSFCP3
LOCAL FIRE
/
FIRE RELAY
/
Water Sensor
/
/
AC PDB-1 SPD
/
/
Power PDB-1 SPD-1
/
/
Power PDB-1 SPD-2
/
/
VESDA Fire 1 Relay-1
/
VESDA Action Relay-1
VLF-250
/
VESDA Fault Relay-1
/
WebUI User
LCD User
Device
Alarm
Name and
Name and
Address
Threshold
Password
Password
/
/
/
/
/
/
/
/
User name: admin
/
/
Initial password:
/
000001
User name: admin
/
/
Initial password:
/
000001
User name: admin
/
/
Initial password:
/
000001
User name: admin
/
/
Initial password:
/
000001
User name: admin
/
/
Password: 000001 FE
Password: Changeme
User name: admin
/
/
Password: 000001 FE
Password: Changeme
1
/
/
/
Normal: closed
/
/
/
Alarm: open
Normal: closed
/
/
/
Alarm: open
Normal: open
/
/
/
Alarm: closed
Normal: open
/
/
/
Alarm: closed
Normal: open
/
/
/
Alarm: closed
Normal: closed
/
/
/
Alarm: open
Normal: closed
/
/
/
Alarm: open
Normal: closed
/
/
/
Alarm: open
Normal: closed
/
/
/
Alarm: open
Normal: open
/
/
/
Alarm: closed
Normal: open
/
/
/
Alarm: closed
Normal: open
/
/
/
Alarm: closed
Port to
DDF
Upper-Level
Upper-Level
Upper-Level
Transfer
Device
Device Port
Device
Port
Smart ETH
POE
/
POE_3
Gateway-1
Smart ETH
LAN
/
POE_4
Gateway-1
Smart ETH
FE
/
POE_1
Gateway-2
Smart ETH
FE
/
POE_2
Gateway-2
Smart ETH
FE
/
POE_3
Gateway-2
Smart ETH
FE
/
POE_4
Gateway-2
Smart ETH
/
POE_1
Gateway-3
Smart ETH
/
POE_2
Gateway-3
COM_IN
/
ECC800-1
COM1
/
/
ECC800-1
AI/DI_1
/
/
ECC800-1
AI/DI_3
/
/
ECC800-1
AI/DI_2
/
/
ECC800-1
AI/DI_4
/
/
ECC800-1
AI/DI_6
/
/
AI/DI Module-1
AI/DI_1
/
/
AI/DI Module-1
AI/DI_2
/
/
AI/DI Module-1
AI/DI_3
/
/
AI/DI Module-1
AI/DI_4
/
/
AI/DI Module-1
AI/DI_7
/
/
AI/DI Module-1
AI/DI_6
/
/
AI/DI Module-1
AI/DI_5
Remarks
WiFi user name: app
Password: Huawei123
Choose Settings > Comm
Settings > IP assigning mode
and select Automatic (DHCP).
Choose Settings > Comm
Settings > IP assigning mode
and select Automatic (DHCP).
Choose Settings > Comm
Settings > IP assigning mode
and select Automatic (DHCP).
Choose Settings > Comm
Settings > IP assigning mode
and select Automatic (DHCP).
Choose Settings > Comm
Settings > IP assigning mode
and select Automatic (DHCP).
Choose Settings > Comm
Settings > IP assigning mode
and select Automatic (DHCP).
Baud rate: 9600
Data bit: 8
Parity bit: None
Stop bit: 1