Performance; Charging Cable Requirements; Network Cable Requirements; Environmental Requirements - LG RESU13 Installation Manual

Table of Contents

Advertisement

2.1.2

Performance

RESU13
Nominal voltage
Operating voltage
Nominal capacity
Total energy
1)
Maximum power
Peak power for 3 seconds
Peak Power for backup Mode
Peak current for 3 seconds
Maximum current
Standard Charge current
Standard Discharge current
Faradic charge efficiency(25°C/ 77°F)
Battery round-trip efficiency
(C/3, 25°C/ 77°F)
Expected lifetime at 25°C/ 77°F
Communication interface
Cooling
1) Actual usable energy at the AC output may vary by condition, such as inverter efficiency
and temperature
2.1.3 Charging cable requirements
Conductor cross-sectional area
Outer diameter
Lug hole size
Lug width
Maximum cable length
2.1.4 Network cable requirements
Category
Connector
2.1.5 Environmental requirements
RESU13
Operating Temperature Range
Optimal Operating Temperature
Storage Temperature Range
Humidity
Altitude
Cooling Strategy
51.8 V
42 ~ 58.8 V
252 Ah
13.048 kWh
5 kW
7 kWp
11 kW for 3sec
166.7 A
119 A
75.6 A
75.6 A
99 %
95 %
More than 10 years
CAN 2.0 B
Natural convection
33 to 50 mm2
14 to 21 mm
M8
21 mm
5 m per cable
Cat 5e
8P8C without any kind of boots
-10 to 50°C (14 to 122°F)
15 to 30°C (59 to 86°F)
-30 to 60°C (-22 to 140°F) : ~ 7 day
-20 to 45°C (-4 to 113°F) : ~ 6 month
5 to 95% (non-condensing)
Max 2,000 m (6,562 ft)
Natural convection
Product Introduction
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eh048252p3s1