Introduction Additional Information SensyMaster FMT230 SensyMaster FMT250 The SensyMaster FMT230 is a top-quality cost- Additional documentation on SensyMaster FMT230, effective solution for the precise and direct FMT250 is available for download free of charge at dynamic mass flow measurement of gases at low www.abb.com/flow.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Table of contents Safety ................4 Transport and storage ..........22 General information and instructions ........4 Inspection ................22 Warnings ..................4 ...
Page 3
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Electrical connections ..........43 Repair ..............102 Safety instructions ..............43 Safety instructions .............. 102 Installing the connection cables .......... 43 Spare parts ................102 ...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 1 Safety Intended use General information and instructions This device can be used in the following applications: These instructions are an important part of the product and • As an insertion sensor for flange mounting pipe must be retained for future reference.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Improper use Cyber security disclaimer The following are considered to be instances of especially This product is designed to be connected to and to improper use of the device: communicate information and data via a network interface. It is •...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 2 Use in potentially explosive atmospheres Note Further information on the approval of devices for use in potentially explosive atmospheres can be found in the type examination certificates or the relevant certificates at www.abb.com/flow.
Note • A specific marking applies, depending on the design. • ABB reserves the right to modify the Ex-marking. Refer to the name plate for the exact marking. ATEX, IECEx and UKCA cFMus Model FMT2xx-A2, U2… in Zone 2, 22 Designation for model FMT2xx-F2…...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 2 Use in potentially explosive atmospheres Temperature data Temperature resistance for the connecting cable Environmental and process conditions for model The temperature at the cable entries of the device is dependent FMT2xx…...
Page 9
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Measuring medium temperature (Ex data) for model FMT2x0-A1… in Zone 1, Zone 21 The table shows the maximum permissible measuring medium temperature as a function of ambient temperature and temperature class.
Page 10
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 2 Use in potentially explosive atmospheres … Temperature data Measuring medium temperature (Ex data) for model FMT2x0-F1… in Class I Division 1 and Class II Division 1 The table shows the maximum permissible measuring medium temperature as a function of ambient temperature and temperature class.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Electrical data Modbus outputs and digital outputs Model ATEX/IECEx: FMT2xx-A1…, FMT2xx-A2…, FMT2xx-A3… Model cFMus: FMT2xx-F1…, FMT2xx-F2… Operating values Type of protection (general) ‘Ex ec’ / ‘NI’ ‘Ex e’ / ‘XP’...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 2 Use in potentially explosive atmospheres Installation instructions ATEX, IECEx and UKCA Use in areas exposed to combustible dust The installation, commissioning, maintenance and repair of When using the device in areas exposed to combustible dusts...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Cable entries in accordance with ATEX/IECEx and UKCA Cable entries in accordance with cFMus The cable glands supplied are ATEX-/IECEx-certified. The use of standard cable glands and seals is prohibited.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 2 Use in potentially explosive atmospheres … Installation instructions Electrical connections Process sealing Note In accordance with ‘North American Requirements for Process The temperature at the cable entries of the device depends on...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Operating instructions Protection against electrostatic discharges DANGER Risk of explosion! The painted surface of the device can store electrostatic charges. As a result, the housing can form an ignition source due to electrostatic discharges in the following conditions: •...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 2 Use in potentially explosive atmospheres … Operating instructions Changing the type of protection – ATEX, IECEx and UKCA When installing in Zone 1, the Modbus interface and digital outputs of the FMT230/250 models can be operated with different types of protection: •...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Changing the type of protection – cFMus The Modbus interface and the digital outputs of the models FMT230/250 can be operated with different types of protection: • When connecting to an intrinsically safe circuit in Div. 1 as an intrinsically safe device (IS).
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 3 Design and function Overview Sensor Figure 3: Sensor FMT230, FMT250 (example) Model FMT230 FMT250 Measuring media Gas and gas mixtures with known composition, see table Available gas types on page 63 Measuring accuracy for gases* ±1.2 % of Qm in the range of 10 to 100 % of the standard...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 3 Design and function Measuring principle Device description Thermal flow metering procedures use different ways to The SensyMaster FMT230, FMT250 works in accordance with the evaluate the flow dependent cooling of a heated resistor as measuring principle of a hot-film anemometer.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 4 Product identification Plates and symbols Name plate Devices which are approved for use in potentially explosive Note atmospheres have an additional warning plate. The name plates displayed are examples. The device identification plates affixed to the device can differ from this representation.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 5 Transport and storage Inspection Check the devices immediately after unpacking for possible If the original packaging material is no longer available, wrap the damage that may have occurred from improper transport.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 6 Installation Installation conditions Safety instructions Installation location and assembly DANGER Note the following points when selecting the installation Danger to life due to piping under pressure! location and when mounting the sensor: Sensors which may eject during installation or removal in •...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation … Installation conditions Inlet and outlet sections Installation at high ambient temperatures The figures below show the recommended inlet and outlet sections for various installations. Figure 10: Mounting position at high ambient temperatures...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Ambient conditions Ambient temperature Maximum operating pressure • Standard: −20 to 70 °C (−4 to 158 °F) • Optional: −40 to 70 °C (−40 to 158 °F) Sensor connection Maximum measuring medium...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation Assembly of the pipe component … Process conditions When installing the pipe components, observe the following Material loads for process connections points: DIN and ASME flanges •...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Wafer type design (FMT091) and partial measuring section (FMT092) 3. Use the appropriate screws for the holes. 4. Slightly grease the threaded nuts. 5. Tighten the nuts in a crosswise manner in accordance with the figure.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation Assembly of the welding adapter with flange or threaded connector Welding adapter with flange connector Dimensions in mm (in) 1 Centering pin 3 Connection flange DN 25 (1 in)
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Weld-on adapter with ball valve Dimensions in mm (in) 1 Centering pin 3 Connection flange DN 25 (1 in) 2 Groove for O-ring 4 Flow direction Figure 19: Dimensions in mm (in) h –...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation … Assembly of the welding adapter with flange or threaded connector Welding adapter with threaded connection in accordance with DIN 11851 Dimensions in mm (in) 1 Union nut...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Additional instructions for welding adapter with ball valve Mounting Consider the following points when installing the welding dater DANGER in the piping: • After welding, the welding adapter must have a length...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation Assembly of the welding adapter with compression ring fitting All dimensions in mm (in) 1 Compression fitting 2 Welding tube for the compression fitting Figure 21: Welding adapter with compression fitting h –...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Preparing the sensor Mounting DANGER Calculation of mounting dimensions Fire hazard in oxygen applications Fire hazard in oxygen applications due to the use of unapproved thread sealing compound. • Use only approved thread sealing compound for oxygen...
Page 34
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation … Assembly of the welding adapter with compression ring fitting First installation of the sensor When mounting the sensor, a distinction is made between first installation and reinstallation. We will address first installation below.
Page 35
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Disassembly and reinstallation of the sensor When mounting the sensor, a distinction is made between first NOTICE installation and reinstallation. We will address reinstallation Damage to the device below. Mechanical damage to the sensor element can occur due to improper disassembly.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation Assembly of the welding adapter with hot tap fitting DANGER Welding design DANGER Explosion hazard Explosion hazard during installation or operation of the Danger to life! integrated hot tap fitting in potentially explosive Danger to life caused by changes to the hot tap fitting.
Page 37
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Calculation of the installation length X and installation depth Y inch X Outside length of the integrated changing device Y Installation depth of the integrated changing device...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation Installing the sensor Wafer type design and welding adapter When installing the sensor, observe the following points: • Installation in the pipe component or welding adapter is only possible if the sensor data matches the measuring point specifications.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Installation / Disassembly of the sensor in connection with the hot tap fitting Safety instructions Overview DANGER Danger to life due to piping under pressure! If the hot tap fitting is in the measurement position during disassembly of the sensor, this may pose a danger to life due to the possibility of the sensor being ejected.
Page 40
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation … Installation / Disassembly of the sensor in connection with the hot tap fitting Disassembly of the sensor Disassembly of the sensor DANGER Danger to life due to leaking measuring medium!
Page 41
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Installing the sensor Note The changing device must be in the disassembly position before disassembling the sensor, the sensor connection is sealed. Figure 32: Removing the protection caps 4. Remove the protection caps Figure 35: Inserting the sensor 1....
Page 42
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 6 Installation … Installation / Disassembly of the sensor in connection with the hot tap fitting Figure 38: Setting the integrated hot tap fitting in measurement position 5. Turn the transmitter with the union nut...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 7 Electrical connections Installing the connection cables Safety instructions Ensure that a drip loop (water trap) is used when installing the DANGER connecting cables for the sensor. Danger of explosion if the device is operated with the...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 7 Electrical connections Position of the terminals Opening and closing the housing WARNING Risk of injury due to live parts! When the housing is open, contact protection is not provided and EMC protection is limited.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Terminal assignment Digital output 41 / 42, 51 / 52 Can be configured via Modbus. Figure 42: Electrical connection PA = functional ground (potential equalization) Connections for the power supply...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 7 Electrical connections … Electrical data for inputs and outputs Modbus® communication Binary output (passive) Note Terminals 41 / 42, 51 / 52 The Modbus® protocol is an unsecured protocol, as such the Output ‘closed’...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C G11603 1 Modbus master 3 Modbus slave 1 2 Terminating resistor 4 Modbus slave n to 32 Figure 44: Communication with the Modbus protocol Cable specification The maximum permissible length is dependent on the baud rate,...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 7 Electrical connections Connection on the device Potential equalization Figure 45: Connection to device Connecting integral mount design Observe the following points when connecting to the power Perform steps supply: •...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 8 Commissioning and operation Write-protection switch, service LED and Safety instructions local operator interface DANGER Danger of explosion if the device is operated with the transmitter housing or terminal box open!
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation Parameterization of the device Checks prior to commissioning Note The following points must be checked before commissioning the • The device does not have the operating elements for device: parameterization on site.
Page 51
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Changing an unknown Modbus slave ID The Modbus Slave ID (address) of the device must be known for Address / data type Description Modbus communication. [register length] Upon delivery, the Modbus Slave ID corresponds to the last two...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Parameterization of the device Parameterization via the local operating interface Field Information Manager (FIM) with the ABB SensyMaster A PC / notebook and the USB interface cable are needed to...
Page 53
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Figure 52: Select FIM – COM-Port 8. Select the corresponding COM port. Close the menu by clicking on “send”. 9. By using the menu button on the left side, the flowmeter is displayed under ‘TOPOLOGY’.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation Interface description NOTICE All Modbus addresses in this chapter are indicated in the format "PLC Base 1". Register tables (overview) Table ID [hex] Table name...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Supported Modbus function codes Overview The function codes listed below are supported by SensyMaster FMT230, FMT250. Function code Description Applicable to register tables 0x02 Read Discrete Inputs Alarm status Discrete Inputs...
… 8 Commissioning and operation … Interface description Modbus function codes In this chapter, all Modbus function codes supported by SensyMaster FMT230, FMT250 are described. 0x02 Read Discrete Inputs The ‘Read Discrete Inputs’ function code is used to read off register ‘Discrete Inputs (Coil)’ of the device.
Page 57
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 0x04 Read Input Registers The ‘Read Input Registers’ function code is used to read off the ‘Input Register’ of the device. The query telegram is designed as follows: Byte Description Slave device code Read Input Registers Function Code, 0x04.
Page 58
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description 0x08 Diagnostics Only the subfunction ‘Return Query Data (0x00, 0x00)’ is supported. If the device receives a query telegram, the telegram is sent back to the Master without changes.
Page 59
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 0x11 Report Slave ID The ‘Report Slave ID’ commando is used to uniquely identify the slave device. The query telegram is designed as follows: Byte Description Slave device code Report Slave ID Function Code, 0x11.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus error handling (exception codes) If the recipient of the message determines an error, it sends an appropriate error message back to the Master. Here the function code from query telegram 0x80 is added.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus data types ABB data type Data type Register count Description ACTION unsigned char One register The data type ‘ACTION’ is used to trigger device functions. Parameters with the data type ‘ACTION’ have no internal memory requirements.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Available units For certain parameters it is possible to choose among the Table 3: Standard density units following units. Selection Code Description...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Table: Gas types for the ApplicationSelector Table 8: Units for the standard volume totalizer Name / Formula Code Selection Code Description Cubic meters Diketene Cubic feet Ethane Liters Ethanol User-definable unit...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Available process variables The process variables available in the software are listed in the table. Note • Some of the process variables can be assigned to the digital outputs DO1 (terminals 41 / 42) and DO2 (terminals 51 / 52), configured as frequency [f] or pulse output [pulse].
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Application of the Health Indication Registers Using the scan register (Condensed Status Registers)) The SensyMaster FMT230, FMT250 has two ‘Scan Register’ via The OI_FMT230_250_EN_C has three ‘Health indication registers’ which groups of parameters can be requested.
Page 66
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Design of the scan register (example) Content of the configuration register (Config scan register) Config scan register 1, register range address 3101 to 3132...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Parameter descriptions Parameter range – Device Info The parameterization of the device can be read out via the Modbus addresses listed here. All Modbus addresses specified here are read only.
Page 68
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Note The numbers in brackets (1 to 8) in the Modbus register addresses correspond to the associated application 1 to 8. Modbus register...
Page 69
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / Description address (application) value range … / Sensor / ...Application 1 ... 8 / ...A1...Temp. meas. – ...A8...Temp. meas. 7199 (1), 7245 (2),...
Page 70
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus register Parameter name Data type [register length] / Description address (application) value range … / Sensor / ...Application 1 ... 8 / ...A1...Gas data – ...A8...Gas data 7163 (1), 7209 (2), Mean Operating Temp.
Page 71
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / Description address (application) value range 6006 (1), 6016 (2), Gas Type 6 TUSIGN8 [1] Gas type and concentration for gas components 1 to 10 of a gas mix.
Page 72
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus register Parameter name Data type [register length] / Description address value range … / ...Transmitter 2011 Transmitter Type TUSIGN8 [1] Display of the transmitter type.
Page 73
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Parameter range – Device Setup Modbus register Parameter name Data type [register length] / Description address value range … / Access Control Read Only Switch TUSIGN8 [1] Indicator of the position of the write protection switch.
Page 74
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Note The numbers in brackets (1 to 8) in the Modbus register addresses correspond to the associated application 1 to 8. Modbus register...
Page 75
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / Description address (application) value range … / Sensor / ...Application 1 ... 8 / ...A1...Temp. meas. – ...A8...Temp. meas. 7199 (1), 7245 (2),...
Page 76
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus register Parameter name Data type [register length] / Description address (application) value range … / Sensor / ...Application 1 ... 8 / ...A1...Gas data – ...A8...Gas data 7163 (1), 7209 (2), Mean Operating Temp.
Page 77
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / Description address (application) value range 6006 (1), 6016 (2), Gas Type 6 Gas type and concentration for gas components 1 ... 10 of a gas mix.
Page 78
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus register Parameter name Data type [register length] / value range Description address … / ...Transmitter 3461 TX Location TAG TUSIGN8 [20] Enter the measuring point tagging for the transmitter.
Page 79
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / value range Description address … / ...Transmitter / ...Units 4013 Unit Massflow Qm TUSIGN8 [1] Selection of unit for mass flow (e.g. for the associated Refer to Table 2: Units for the mass flow on parameters and the corresponding process values).
Page 80
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus register Parameter name Data type [register length] / value range Description address … / ...Transmitter / ...Custom Units 3481 Mass flow Qm Name TCHAR [8] Enter a name for the user-defined unit Qm.
Page 81
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Parameter range - Output Modbus register Parameter name Data type [register length] / value Description address range … / ...Dig.Out 41/42 4043 Mode TUSIGN8 [1] Selection of the operating mode for the digital output 41 / 42.
Page 82
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus register Parameter name Data type [register length] / Description address value range … / ...Dig.Out 41/42 / ...Binary Out 41/42 The following parameters are only available if the digital output 41 / 42 has been configured as a binary output.
Page 83
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / value Description address range … / ...Dig.Out 51/52 / ...Freq.Out 51/52 The following parameters are only available if the digital output 51 / 52 has been configured as a frequency output.
Page 84
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Parameter range – Process Alarm Modbus register Parameter name Data type [register length] / Description address value range 0 to 95 Diagnosis register TUSIGN8 [1] Display of the alarm history.
Page 85
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Parameter range – Communication Modbus register Parameter name Data type [register length] / Description address value range … / ...Modbus 4007 Device Address TUSIGN8 [1] Setting of the Modbus device address.
Page 86
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Parameter range – Diagnostics Modbus register Parameter name Data type [register length] / value Description address range ... / ...Diagnosis Control 3313 Preset Maint.
Page 87
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / Description address value range Setting of the simulated measured values. The simulated value is selected with the parameter ‘Simulation Switch’. 4003 Dig.Out 41/42 State...
Page 88
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Modbus register Parameter name Data type [register length] / value Description address range ... / ...SensorCheck These parameters are only available when the VeriMass function is activated.
Page 89
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus register Parameter name Data type [register length] / value Description address range ... / ...Alarm Simulation 4002 Alarm Simulation TUSIGN8 [1] Manual simulation of alarms / error messages. 0: Aus The simulated alarm is selected by setting the parameter to the 1: Mass flowrate exceeds limits.
Page 90
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation … Interface description Parameter range – Totalizer Modbus register Parameter name Data type [register length] / Description address value range ... / ...Operation 9007 Start all Totalizer ACTION [1] Start all counters of the device.
Sets the time for the overrun quantity correction after the fill valve is closed. 0.1 to 10 s Factory setting: 0.1 s Software history In accordance with NAMUR recommendation NE53, ABB offers a transparent and traceable software history. Device software package FMT2xx Version Issue date...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 8 Commissioning and operation FillMass batch function Only with FMT250 The integrated FillMass fill function allows filling operations with filling times of > 3 s. For this purpose, the filling quantity is given via an adjustable totalizer.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Fill operation Filling process run The following steps must be performed for every fill operation: Initialization The following steps must be performed before the initial start of a filling operation and e.g. in case of changes to the fill quantity:...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 9 Diagnosis / error messages NOTICE All Modbus addresses in this chapter are indicated in the format "PLC Base 1". General Errors encountered are itemized in tabular form on the following pages. The response of the transmitter on error detection is described therein.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Overview The states of the process variables and counters are represented by symbols; please see the table below. Symbol Description Counter stop – No change, current value Priority Failure Error text...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 9 Diagnosis / error messages Alarm status and alarm history status Modbus address Byte / Error no. Error text Description NAMUR classification bit pos. Active History 1 / 2 F084.010...
Page 97
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Modbus address Byte / Error no. Error text Description NAMUR classification bit pos. Active History 5 / 3 S046.042 Dig.Out 51/52 is saturated. Digital output 51 / 52 (pulse output) maximum pulse Out of specification rate up-scaled.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 9 Diagnosis / error messages ‘SensorCheck’ diagnosis function SensorCheck compares the characteristic values of the installation fingerprint with those of the current device fingerprint. As a result, changes to the sensor element such as contamination or damage, for example, can be detected early on and the integrity of the measurement can be guaranteed.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 10 Maintenance Safety instructions DANGER CAUTION Danger of explosion if the device is operated with the Risk of burns due to hot measuring media transmitter housing or terminal box open! The device surface temperature may exceed 70 °C (158 °F),...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 10 Maintenance Cleaning 4. Carefully clean the measuring element with warm water or an When cleaning the exterior of meters, make sure that the alcohol solution using a soft brush or cotton swab.
Page 101
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 1. Disassemble the sensor (see Disassembly of the sensor on page 40). 2. Loosen the fixing screws of the union nut and pull the guide tube out of the changing device. Clean the guide tube if necessary.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 11 Repair Safety instructions DANGER CAUTION Danger of explosion if the device is operated with the Risk of burns due to hot measuring media transmitter housing or terminal box open! The device surface temperature may exceed 70 °C (158 °F),...
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Replacing the fuse Returning devices NOTICE Use the original packaging or a secure transport container of an appropriate type if you need to return the device for repair or If the O-ring gasket is seated incorrectly or damaged, this recalibration purposes.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 12 Recycling and disposal Disposal Dismounting Note WARNING Products that are marked with the adjacent symbol Risk of injury due to process conditions. may not be disposed of as unsorted municipal waste The process conditions, for example high pressures and (domestic waste).
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 13 Specification Note The device data sheet is available in the ABB download area at www.abb.com/flow. 14 Additional documents Note All documentation, declarations of conformity, and certificates are available in ABB's download area.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C 15 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C FMT200 Installation diagram 3kxf000094G0009 Page 1 of 5...
Page 108
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 15 Appendix … FMT200 Installation diagram 3kxf000094G0009 Page 2 of 5...
Page 109
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Page 3 of 5...
Page 110
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C … 15 Appendix … FMT200 Installation diagram 3kxf000094G0009 Page 4 of 5...
Page 111
SensyMaster FMT230, FMT250 THERMAL MASS FLOWMETER | OI/FMT230/250-EN REV. C Page 5 of 5...
Page 112