24
PCS100 AVC-20 User Manual
4.9 Enclosure
Enclosure rating
Material
Panel thickness
Side and rear
Door
Finish
Color
Enclosure access
4.10 Service
MTTR
Diagnostics
Remote monitoring
4.11 Power Quality Event Monitor
Events recorded
Event detection
Sag threshold
Surge threshold
Accuracy
Remote monitoring
Remote notification
4.12 User Interface
User interface
Touch panel
Control inputs
Control outputs
Communication
IP20
Electro-galvanized steel
1.5 mm
2 mm
Standard epoxy-polyester powder coating textured finish.
RAL7035
Hinged doors with key lock
30 min typical by module exchange
Non-volatile event & service log
E-mail
Voltage Sag (RMS)
Voltage Surge (RMS)
Input Voltage
90% of Utility voltage default setting (user adjustable)
110% of Utility voltage default setting (user adjustable)
Voltage: ± 2%
Duration: 10 ms
Web Server
E-mail
10.1" color touch panel
Full parameter control
Start / Stop / Reset digital inputs
Running, Warning and Fault relays
Ethernet
Modbus TCP
E-mail