11.3 Stop – Enable Switch
A Stop-Enable switch is mounted inside of the Master Controller Enclosure as a failsafe device.
In case of any user interface display or remote-control failure this switch can be used to stop the PCS100 AVC-20
operating and put it into BYPASS mode by setting to STOP. This will inhibit PCS100 AVC-20 from starting.
This switch is wired in series with the remote inhibit input above.
Returning this switch to Enable will enable the controller but not start it. A local or remote start is needed to bring
the system out of BYPASS.