Load - Output; Performance; Internal Bypass; Injection Transformer - ABB PCS100 AVC-20 User Manual

Active voltage conditioner
Table of Contents

Advertisement

22
PCS100 AVC-20 User Manual
4.3 Load – Output
Voltage
Equivalent series impedance
Displacement power factor
Crest factor
Overload capability from 100% supply
voltage

4.4 Performance

Efficiency
Sag correction response
Voltage regulation time
Voltage regulation accuracy
Continuous undervoltage regulation range
Continuous overvoltage regulation range

4.5 Internal Bypass

Capacity
Maximum overload capacity
(in bypass)
Transfer time
Equivalent series impedance

4.6 Injection Transformer

Transformer type
Insulation
Frequency
Vector group
To match nominal input voltage
Note: output voltage can be adjusted by ± 10% with 0.1% steps
< 4% (model specific)
0 lagging to 0.9 leading
3.0
150% for 30 seconds, once every 500 s
Typically, > 98%
< 250 µs
< 20 ms for any voltage deviation within the
specification
±1% typical, ±2% max.
-15% with load power factor 1.0
-20% with load power factor 0.75
+20%
100% of model rating (kVA)
125% for 10 minutes
150% for 1 minute
500% for 1 s
2000% for 200 ms
To Bypass < 0.5 ms
To Inverter < 250 ms
bypass < 2.5% typical
Dry
IEC 60085 Thermal class 200
50 Hz and 60 Hz
Diii (delta + 3 independent windings)