ABB PCS100 AVC-20 User Manual page 75

Active voltage conditioner
Table of Contents

Advertisement

PCS100 AVC-20 User Manual
Code
Origin
Type
71
R,I
F
72
R, I
W
73
R, I
F
75
M
F
76
M
F
77
R,I
W
78
M
F
79
R, I
W
80
R, I
F
81
M, R
AB
82
R
AB
83
M
F
GDM Info
Description
Master Lost
The rectifier or inverter lost
communication with master
module.
Module
Two consecutive frames
Comms
have been lost from the
Warning
Streaming Data Interface.
Module
The Streaming Data
Comms Fault
Interface frame loss
exceeds the threshold.
PC Comms
Master lost
Lost
communications with
critical TCPM (PC).
GDM Lost
Master lost
communications with
critical GDM.
Module
A module has been
Address
replaced. The replacement's
Changed
number was not
recognized.
Module
Number of rectifier and
Number
inverter modules is
Mismatch
unequal.
Module
There are sustainable
Display
communication errors
Warning
between the module display
board and Digital Signal
Processor Engine (DSPE).
Module
There were unsustainable
Display Error
communication errors
between the module display
board and the Module DSPE
(Digital Signal Processor
Engine).
Inverter AC
The input voltage is below
Voltage Low
the operation threshold.
Note: This is normal when
the input voltage is
removed or applied.
Utility Open
Utility open source
Source
detected. Input has been
switched off.
IOM
Commissioning test mode
Testmode
has been activated.
Setting: 915 Relay Test
Modes
Recommended Action
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Ensure all communication
ribbon cables are connected
and not damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Check the PC connections.
Check the GDM connections.
If a module has been replaced
check the module ID number is
set to the same as the
replaced module.
- Ensure module IDs are set
correctly
- Call service agent
Ensure the module display
board is firmly plugged into
interface board.
Ensure the module display
board is plugged firmly into
interface board.
Check utility voltage is within
the thresholds.
Check input breaker.
When the test has been
completed switch off the test
mode
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcs100 avc-40

Table of Contents