Haier YR-E20 Operation & Installation Manual page 32

Wired controller

Advertisement

2. Wired controller runs as no non-volatile memory function
if the EEPROM is broken, even if you set the non-volatile
memory function.
3. No matter non-volatile memory is valid or invalid,error
code,ECO parameter and temperature compensation will
be remembered.
Temperature Compensation
1. Under off state and backlight is on, keep pressing fan key for
10 seconds, compensation parameter and
The default data is 00. When in celsius system,ambient
compensation value is from -04 to 04,while in fahrenheit
system,ambient compensation value being from -07 to 07,
then press function key to confirm the setting.
2. The compensation is valid only when SW3 is OFF, that is to
say, it is valid when wired controller sensor is valid.
Forced Cooling
Press ON/OFF key within 5 s in off state to turn on the unit
with buzzer buzzing 2 times.
Keep pressing ON/OFF key for 5 seconds, the buzzer sounds
2 times. The unit enters forced cooling mode, then the state is
on, cooling mode, 16°C, high speed. LL is displayed instead of
set/ambient temperature, and LL is flashing. Press any key or
receive remote signals to exit the forced cooling mode.
31
are displayed.