(2) Operating procedure
Start settings on the I/O assignment setting window of GX developer.
(a) I/O assignment setting window
Set the following to the slot where QJ61CL12 is installed.
The "Type" setting is indispensable; set other items as needed.
Type
Model
Points
Start XY
Detailed setting
(b) Intelligent function module switch setting window
Open the following window to set "Switch 1".
The setting can easily be made if the value is entered in decimal. Change the entry format to decimal notation.
48
Downloaded from
ManualsNet.com
[Parameter]
[PLC Parameter]
Item
Select "Intelli".
Enter the model name of the module.
Select the number of occupied I/O points.
Enter the start I/O number of QJ61CL12.
Specify the control CPU of QJ61CL12.
Because "Error time output mode" or "H/W error time Programmable controller operation
mode" are invalid for QJ61CL12, these settings are not required.