Download Print this page

Mitsubishi Electric 800 Series Instruction Manual page 50

Hide thumbs Also See for 800 Series:

Advertisement

(1)
Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with neighboring wires. If the length is too
short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
(2)
Crimp the terminals by inserting the wires into a blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is inappropriate, or the face is damaged.
• Blade terminals commercially available (as of May 2016)
2
Cable gauge (mm
)
With insulation
sleeve
0.3
AI 0,34-10TQ
0.5
AI 0,5-10WH
0.75
AI 0,75-10GY
1
AI 1-10RD
1.25, 1.5
AI 1,5-10BK
0.75 (for two wires)
AI-TWIN 2×0,75-10GY

A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.

Applicable for terminals A1, B1, C1, A2, B2, and C2.
Blade terminal product
2
Cable gauge (mm
)
0.3 to 0.75
BT 0.75-11
(3)
Insert the wires into a socket.
• Wire removal
Pull the wire while pushing the open/close button all the way down firmly with a flathead screwdriver.
NOTE
• When using stranded wires without a blade terminal, twist enough to avoid short circuit with a nearby terminals or wires.
• During wiring, pulling out the wire forcefully without pushing the open/close button all the way down may damage the terminal block.
• Use a small flathead screwdriver (tip thickness: 0.4 mm, tip width: 2.5 mm).
If a flathead screwdriver with a narrow tip is used, terminal block may be damaged.
Commercially available products (as of February 2016) .
Name
Model
Driver
SZF 0- 0,4 x 2,5
• Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause an inverter damage or injury.
Cable sheath stripping length
Ferrule terminal model
Without insulation
sleeve
A 0,75-10
A 1-10
A 1,5-10
Insulation cap
number
product number
VC 0.75
When using a single wire or stranded wires without a blade terminal, push the open/close button all the
way down with a flathead screwdriver, and insert the wire.
Manufacturer
Phoenix Contact Co., Ltd.
Crumpled tip
Damaged
Manufacturer
For UL wire

AI 0,5-10WH-GB
AI 0,75-10GY-GB
Phoenix Contact Co., Ltd.
AI 1-10RD/1000GB
AI 1,5-10BK/1000GB

Manufacturer
product number
NICHIFU Co., Ltd.
NH 69
Open/close button
Flathead screwdriver
Control circuit terminal
Unstranded
wires
Wires are not inserted
into the sleeve
Crimping tool
name
CRIMPFOX 6
Crimping tool
Open/close button
Flathead screwdriver
WIRING
11

Advertisement

loading