Parameter list
Setting
Pr.
Name
Second PID display
1137
0 to 300%
bias analog value
Second PID display
1138
0 to 500, 9999 9999
gain coefficient
Second PID display
1139
0 to 300%
gain analog value
Second PID set point/
1140
deviation input selection 1 to 5
Second PID measured
1 to 5, 101 to
1141
value input selection
105
1142
Second PID unit selection 0 to 43, 9999
1143
Second PID upper limit 0 to 100%, 9999 9999
1144
Second PID lower limit 0 to 100%, 9999 9999
Second PID deviation
0.0 to 100.0%,
1145
limit
9999
Second PID signal
1146
0 to 3, 10 to 13 0
operation selection
Second output interruption
0 to 3600s,
1147
detection time
9999
Second output interruption
1148
0 to 590Hz
detection level
Second output
1149
interruption cancel level 900 to 1100% 1000%
1150 to
User parameters 1 to 50 0 to 65535
1199
PID gain tuning timeout
1211
1 to 9999s
time
Step manipulated
1212
900 to 1100% 1000%
amount
Step response
1213
0.01 to 600s
sampling cycle
Timeout time after the
1214
1 to 9999s
maximum slope
Limit cycle output upper
1215
900 to 1100% 1100%
limit
Limit cycle output lower
1216
900 to 1100% 1000%
limit
1217
Limit cycle hysteresis
0.1 to 10%
0, 100 to 102,
111, 112, 121,
1218
PID gain tuning setting
122, 200 to
202, 211, 212,
221, 222
PID gain tuning start/
(0), 1, 8, (9,
1219
status
90 to 96)
1300 to
1343,
Communication option parameters
1350 to
1359
Detection time for PID
1361
0 to 900s
output hold
1362
PID output hold range
0 to 50%, 9999 9999
0 to 360s,
1363
PID priming time
9999
1364
Stirring time during sleep 0 to 3600s
1365
Stirring interval time
0 to 1000h
1366
Sleep boost level
0 to 100%, 9999 9999
1367
Sleep boost waiting time 0 to 360s
Output interruption
1368
0 to 360s
cancel time
Check valve closing
0 to 120Hz,
1369
completion frequency
9999
Detection time for PID
1370
0 to 900s
limiting operation
PID upper/lower limit
1371
0 to 50%, 9999 9999
pre-warning level range
PID measured value
1372
control set point change
0 to 50%
amount
PID measured value
1373
control set point change
0 to 100%
rate
Auxiliary pressure pump
1374
900 to 1100% 1000%
operation starting level
Auxiliary pressure pump
1375
900 to 1100% 1000%
operation stopping level
Auxiliary motor
0 to 100%,
1376
stopping level
9999
PID input pressure
1377
1 to 3, 9999
selection
PID input pressure
1378
0 to 100%
warning level
PID input pressure fault
0 to 100%,
1379
level
9999
PID input pressure
1380
warning set point
0 to 100%
change amount
PID input pressure fault
1381
0, 1
operation selection
Starting times lower 4
1410
0 to 9999
digits
22
BASIC OPERATION
Initial
Pr.
range
value
Starting times upper 4
20%
1411
digits
Motor induced voltage
1412
constant (phi f) exponent 0 to 2, 9999
Second motor induced
100%
1413
voltage constant (phi f)
exponent
2
Ethernet communication
1424
network number
3
Ethernet communication
1425
station number
9999
Link speed and duplex
1426
mode selection
9999
Ethernet function
1427
selection 1
1s
Ethernet function
1428
selection 2
0Hz
Ethernet function
1429
selection 3
0
100s
Ethernet signal loss
1431
detection function
selection
Ethernet communication
1432
check time interval
1s
1434
Ethernet IP address 1
10s
1435
Ethernet IP address 2
1436
Ethernet IP address 3
1437
Ethernet IP address 4
1%
1438
Subnet mask 1
1439
Subnet mask 2
0
1440
Subnet mask 3
1441
Subnet mask 4
0
1442
Ethernet IP filter address 1 0 to 255
1443
Ethernet IP filter address 2 0 to 255
1444
Ethernet IP filter address 3 0 to 255
5s
1445
Ethernet IP filter address 4 0 to 255
Ethernet IP filter address
1446
2 range specification
9999
Ethernet IP filter address
1447
3 range specification
15s
Ethernet IP filter address
1448
4 range specification
0h
Ethernet command source
1449
selection IP address 1
Ethernet command source
1450
0s
selection IP address 2
Ethernet command source
1451
0s
selection IP address 3
Ethernet command source
1452
9999
selection IP address 4
Ethernet command source
0s
1453
selection IP address 3
range specification
Ethernet command source
1454
selection IP address 4
range specification
5%
1455
Keepalive time
1460
PID multistage set point 1
1461
PID multistage set point 2
0%
1462
PID multistage set point 3
1463
PID multistage set point 4
1464
PID multistage set point 5
1465
PID multistage set point 6
1466
PID multistage set point 7
9999
Number of cleaning
1469
times monitor
Number of cleaning
9999
1470
times setting
20%
1471
Cleaning trigger selection 0 to 15
Cleaning reverse
1472
9999
rotation frequency
Cleaning reverse
1473
rotation operation time
5%
Cleaning forward
1474
rotation frequency
0
Cleaning forward
1475
rotation operation time
0
1476
Cleaning stop time
Setting
Initial
Name
range
value
0 to 9999
0
9999
0 to 2, 9999
9999
1 to 239
1
1 to 120
1
0 to 4
0
502, 5000 to
5002, 5006 to
5008, 5010 to
5001
5013, 9999,
45237, 61450
502, 5000 to
5002, 5006 to
5008, 5010 to
45237
5013, 9999,
45237, 61450
502, 5000 to
5002, 5006 to
5008, 5010 to
9999
5013, 9999,
45237, 61450
0 to 3
0
0 to 999.8s,
9999
9999
0 to 255
192
0 to 255
168
0 to 255
50
0 to 255
1
0 to 255
255
0 to 255
255
0 to 255
255
0 to 255
0
0
0
0
0
0 to 255, 9999 9999
0 to 255, 9999 9999
0 to 255, 9999 9999
0 to 255
0
0 to 255
0
0 to 255
0
0 to 255
0
0 to 255, 9999 9999
0 to 255, 9999 9999
1 to 7200s
3600s
9999
9999
9999
0 to 100%,
9999
9999
9999
9999
9999
0 to 255
0
0 to 255
0
0
0 to 590Hz
30Hz
0 to 3600s
5s
0 to 590Hz,
9999
9999
0 to 3600s,
9999
9999
0 to 3600s
5s
Setting
Pr.
Name
range
Cleaning acceleration
0 to 3600s,
1477
time
9999
Cleaning deceleration
0 to 3600s,
1478
time
9999
1479
Cleaning time trigger
0 to 6000hr
0, 1, (2, 3, 4, 5,
Load characteristics
1480
81, 82, 83, 84,
measurement mode
85)
Load characteristics
0 to 400%,
1481
load reference 1
8888, 9999
Load characteristics
0 to 400%,
1482
load reference 2
8888, 9999
Load characteristics
0 to 400%,
1483
load reference 3
8888, 9999
Load characteristics
0 to 400%,
1484
load reference 4
8888, 9999
Load characteristics
0 to 400%,
1485
load reference 5
8888, 9999
Load characteristics
1486
0 to 590Hz
maximum frequency
Load characteristics
1487
0 to 590Hz
minimum frequency
Upper limit warning
0 to 400%,
1488
detection width
9999
Lower limit warning
0 to 400%,
1489
detection width
9999
Upper limit fault
0 to 400%,
1490
detection width
9999
Lower limit fault
0 to 400%,
1491
detection width
9999
Load status detection
signal delay time / load
1492
0 to 60s
reference measurement
waiting time
1499
Parameter for manufacturer setting. Do not set.
Pr.CLR Parameter clear
(0, )1
ALL.CL All parameter clear
(0, )1
Err.CL Fault history clear
(0, )1
Pr.CPY Parameter copy
(0, )1 to 3
Pr.CHG Initial value change list ―
IPM
IPM initialization
0, 12
Automatic parameter
AUTO
setting
Pr.Md Group parameter setting (0, )1, 2

Differs according to capacities.
• 6%: FR-F820-00046(0.75K) and FR-F840-
00023(0.75K)
• 4%: FR-F820-00077(1.5K) to 00167(3.7K) and FR-
F840-00038(1.5K) to 00083(3.7K)
• 3%: FR-F820-00250(5.5K), 00340(7.5K), FR-F840-
00126(5.5K) and 00170(7.5K)
• 2%: FR-F820-00490(11K) to 01540(37K) and FR-
F840-00250(11K) to 00770(37K)
• 1.5%: FR-F820-01870(45K), 02330(55K), FR-F840-
00930(45K) and 01160(55K)
• 1%: FR-F820-03160(75K) or higher and FR-F840-
01800(75K) or higher

For FR-F820-02330(55K) or lower and FR-F840-
01160(55K) or lower

For FR-F820-03160(75K) or higher and FR-F840-
01800(75K) or higher

For FR-F820-00340(7.5K) or lower and FR-F840-
00170(7.5K) or lower

For FR-F820-00490(11K) or higher and FR-F840-
00250(11K) or higher

Differs according to capacities.
• 4%: FR-F820-00340(7.5K) or lower and FR-F840-
00170(7.5K) or lower
• 2%: FR-F820-00490(11K) to 02330(55K) and FR-
F840-00250(11K) to 01160(55K)
• 1%: FR-F820-03160(75K) or higher and FR-F840-
01800(75K) or higher

Differs according to the voltage class. (200 V class/400
V class)

The parameter number in parentheses is the one for
use with the LCD operation panel and parameter unit.

Differs according to types. (FM type/CA type)

The setting is available only with the CA type.

The setting value "60" is only available for Pr.178, and
"61" is only for Pr.179.

The setting values "92, 93, 192, 193" are only available
for Pr.190 to Pr.194.

Simple mode parameters. (When Pr.160 = "9999", only
the simple mode parameters are displayed.)
Initial
value
9999
9999
0
0
9999
9999
9999
9999
9999
60/50Hz

6Hz
20%
20%
9999
9999
1s
0
0
0
0
0
0