ABB SPAU 130 C User Manual And Technical Description
ABB SPAU 130 C User Manual And Technical Description

ABB SPAU 130 C User Manual And Technical Description

Three-phase overvoltage and undervoltage relay

Advertisement

Quick Links

SPAU 130 C
Three-phase overvoltage and
undervoltage relay
User´s manual and Technical description
= 100V 110V
U
n
SPCU 3C14
REGISTERS
0 0 0 0
1
2
3
4
5
6
7
8
RS 422
f
n = 50Hz
SPAU 130 C
80...265V ~ –
18...80V –
>
/
U
U
n
/
U
U
n
max
<
/
SGR
U
U
n
U
/
U
n
min
(
>
)
n
U
(
)
n
<
U
>
[
]
t
t
%
/
[
]
<
t
/
t
%
0
Ser.No.
2
U
12
5
60Hz
STEP
U
>
U
aux
U
n
0.8
t
[ ]
>
s
k
0.05
U
<
U
1
n
2
0.4
3
4
5
6
7
8
t [ ]
<
s
1
1.0
>
U
U
<
U
U
IRF
23
31
1.2
STEP
1.6
0.5
SG1
1
1.0
2
3
4
5
0.8
6
7
8
0
1
1.2
RESET
5.0
12
U
U
>
<
SPCU 3C14

Advertisement

Table of Contents
loading

Summary of Contents for ABB SPAU 130 C

  • Page 1 SPAU 130 C Three-phase overvoltage and undervoltage relay User´s manual and Technical description > < = 100V 110V n = 50Hz 60Hz SPAU 130 C STEP 80...265V ~ – > 18...80V – STEP SPCU 3C14 REGISTERS > 0 0 0 0 0.05...
  • Page 2: Table Of Contents

    Ordering numbers ......................21 Dimensions and mounting ................... 22 Order information ......................22 The complete manual for the combined overvoltage and undervoltage relay SPAU 130 C includes the following submanuals: Three-phase overvoltage and undervoltage relay, general part 1MRS 750638-MUM EN...
  • Page 3 EXTERNAL BLOCKING FUNCTION FOR THE UNDERVOLTAGE STAGE BLOCKING SERIAL I/O SERIAL COMMUNICATION Fig. 1. Protection functions of the combined overvoltage and undervoltage relay SPAU 130 C. The encircled numbers refer to the ANSI (=American National Standards Institute) number of the concerned protection function.
  • Page 4 3 2 4 t>,k> 3U> SGB/5 t< 3U< SPAU 130 C Fig. 2. Connection diagram for the combined overvoltage and undervoltage relay SPAU 130 C Auxiliary voltage A,B,C,D,E Output relays Self-supervision signal Start signal Trip signal Switchgroup for configuring trip and alarm signals...
  • Page 5 Fig.3. Rear view of the overvoltage and undervoltage relay SPAU 130 C Specification of input and output terminals Contacts Function 13-14 Phase-to-phase voltage U (100 V) 13-15 Phase-to-phase voltage U (110 V) 16-17 Phase-to-phase voltage U (100 V) 16-18 Phase-to-phase voltage U...
  • Page 6 The trip signals of the U> stage is firmly wired ing functions can be selected with the switches Configuration of to output relay A and the trip signal of the U< of the SGR switchgroup on the front panel of output relays stage to output relay B.
  • Page 7: Function

    = 100V 110V n = 50Hz 60Hz voltage value is currently being displayed. SPAU 130 C 3. The red IRF indicator of the self-supervision STEP 80...265V ~ – > system indicates, when lit, that a permanent 18...80V –...
  • Page 8: Technical Data

    Technical data Energizing inputs 100 V 110 V Terminals 13-14, 16-17, 19-20 13-15, 16-18, 19-21 Rated voltage U 100 V 110 V Continuous voltage withstand 2 x U 2 x U Power consuption at U <0.5 VA Rated frequency f acc.
  • Page 9 Combined overvoltage and undervoltage relay module SPCU 3C14 - see "Technical data" in the manual for the module. Data communication Transmission mode Fibre optic serial bus Data code ASCII Selectable data transfer rates 300, 1200, 2400, 4800 or 9600 Bd Fibre optic bus connection module, powered from the host relay - for plastic fibre cables...
  • Page 10: Examples Of Applications

    3U< SPAU 130 C Fig. 4. Substation overvoltage and undervoltage protection with voltage relay SPAU 130 C. The selector switch positions are shown in the table on the following page. The overvoltage and undervoltage relay module Thus the overvoltage stage provides an alarm...
  • Page 11 0 not in use 0 no trip signal of stage U> to output relay B Σ When the switches are set as above, the output relays of the voltage relay SPAU 130 C provide the following signals: Contact Function 65-66 Tripping of the circuit breaker on the high-voltage side of the transformer (U>)
  • Page 12 3U< SPAU 130 C Fig. 5. Motor feeder undervoltage protection with relay SPAU 130 C. The selector switch positions are shown in the table on the following page. The undervoltage stage of the relay trips the An unwanted operation of the undervoltage...
  • Page 13 0 not in use 0 no trip signal of stage U> to output relay B Σ When the switches are set as above, the output relays of the voltage relay SPAU 130 C provide the following signals: Contact Function 65-66 Tripping of the main circuit breaker (U>)
  • Page 14 Example 3. Generator pole short-circuit protection 100V 110V 100V 110V 100V 110V Fig. 6. Generator pole short-circuit protection with relays SPAU 130 C and SPAJ 131 C. The selector switch positions are shown in the table on the following page.
  • Page 15 0 not in use 0 no trip signal of stage U> to output relay B Σ When the switches are set as above, the output relays of the voltage relay SPAU 130 C provide the following signals: Switch Function 65-66 Tripping of the generator circuit breaker and the excitation circuit breaker on pole short circuit (stages U<...
  • Page 16 Recorded data and The registers of the overvoltage and under- given via the serial bus or by pressing the STEP fault analysis voltage relay contain useful information about and RESET push-buttons simultaneously. the behaviour of the power network during normal service and in a fault situation. The number of startings, register 5 and 6, pro- vides information on the occurance of On starting of the overvoltage stage the maxi-...
  • Page 17 Relay testing, both primary and secondary, When the auxiliary voltage is connected to the Secondary should always be performed in accordance with relay, a self-testing program is carried out auto- injection testing national regulations and instructions. matically. The self-testing program includes the whole relay except for the matching transform- The protection relay incorporates an IRF func- ers and the contacts of the output relays.
  • Page 18 100V 110V 100V Fig. 7. Test circuit for the overvoltage and undervoltage relay SPAU 130 C. When the test circuit has been completed and function of the test circuit can be verified by the selector switches properly set, the auxiliary means of a multimeter.
  • Page 19 Checking the matching transformers Checking the start function The three matching transformers of the relay are Apply test voltage to terminals 13-14 or 13-15 checked one by one. Apply voltage to the relay depending on the used energizing input. Close and compare the voltage value read from the switch S1 and increase the voltage slowly until display of the relay with the voltage value shown...
  • Page 20 Checking the undervoltage stage U< Operate time t< Set the switches of the SGR switchgroup as Definite time characteristic follows before starting the test: Set the test voltage at 0.5 times the set start Switch Position voltage of the undervoltage stage. The timer is started by switch S1, when it is closed and stopped by contact 68-69, when output relay B picks up.
  • Page 21: Ordering Numbers

    SPA-ZC 17_ or SPA-ZC 21_ Combined overvoltage and undervoltage relay Ordering numbers SPAU 130 C RS 422 020 -AA, CA, DA, FA Combined overvoltage and undervoltage relay including test adapter RTXP 18 SPAU 130 C RS 422 220 -AA, CA, DA, FA...
  • Page 22: Dimensions And Mounting

    SPA-ZX 111 SPA-ZX 112 SPA-ZX 113 Fig. 8. Dimensions of the overvoltage and undervoltage relay SPAU 130 C The relay case is made of profile aluminium and the edge of the cover provides an IP 54 degree of finished in beige.
  • Page 23 SPCU 3C14 Combined overvoltage and undervoltage relay module User´s manual and Technical description > < STEP > STEP > 0.05 < RESET t [ ] < > < SPCU 3C14...
  • Page 24 SPCU 3C14 1MRS 750510-MUM EN Issued 96-12-02 Combined overvoltage Modified 99-12-20 Version D (replaces 34 SPCU 7 EN1) and undervoltage Checked KJ Approved MN relay module Data subject to change without notice Features .......................... 2 Contents Description of operation ....................3 Block diagram .........................
  • Page 25 The combined overvoltage and undervoltage time is programmed with switches SG1/4 and 5. Description of module SPCU 3C14 is a three-phase relay mod- At inverse time characteristic two different sets operation ule, which can be programmed for single-phase of voltage/time curves, called A and B, can be operation by means of switch SG1/1 on the selected by means of switch SG1/4.
  • Page 26: Block Diagram

    Block diagram Fig. 2. Block diagram for combined overvoltage and undervoltage relay module SPCU 3C14. Measured phase-to-phase voltages BS1, BS2, BS3 Blocking signals BTS2 Blocking of the tripping of the U< stage Front panel programming switchgroup Software selector switchgroup for defining the mode of function of the start and operation indicators Selector switchgroup for configuration of blockings (on the PC-board) Start signal of the U>...
  • Page 27 Front panel > Simplified module symbol < Self-supervision alarm Indicators for measured voltages indicator Numerical display STEP > Setting knob and indicator for STEP starting value of stage U> Display step push-button Setting knob and indicator for > operate time t> or time multiplier k> 0.05 of stage U>...
  • Page 28: Settings

    The setting values are shown by the three lit, the setting value currently being shown on Settings rightmost green digits of the display. The LED the display. indicator below the setting knob shows, when U>/U Start value of the U> stage as a multiple of the rated voltage of the relay energizing input.
  • Page 29 Switch Function SG1/6 Selection of automatic blocking of starting and tripping of the undervoltage stage U<. When SG1/6 = 0, the undervoltage stage always operates when a measured voltage falls below the setting value. When SG1/6 = 1, starting and tripping of the undervoltage stage are blocked if one of the measured voltages, falls to a value below 0.2 x U This feature can be used for preventing unnecessary startings and trippings during auto-reclose sequences.
  • Page 30: Measured Data

    The measured values are presented with the data being presented are indicated by LED Measured data rightmost three green digits on the display. The indicators on the front panel. Indicator Measured data The U voltage measured by the module expressed as a multiple of the rated voltage of the relay energizing input.
  • Page 31 Register/ Recorded information STEP Display of blocking signals and other external control signals. The digit at the extreme right indicates the state of the blocking of the undervoltage stage. The following states are indicated: 0 = no blockings 2 = tripping of the undervoltage stage blocked The middle digit of the register is always a zero.
  • Page 32: Menu Chart

    Menu chart MAIN MENU SUBMENU STEP 0,5 s RESET 1 s Display off. Normal state Voltage U measured = parameter that can be set in the setting mode Voltage U measured STEP BACKWARD 0,5 s STEP FORWARD 1 s Voltage U measured SUBMENU Remotely set...
  • Page 33 At inverse time characteristic the operate time At an IDMT mode of operation the recording of Voltage/time of the overvoltage stage will be shorter the the tripping time of the overvoltage stage does characteristic greater the deviation from the setting value. not start until the voltage exceeds the setting (Modified 99-10) value by 6%.
  • Page 34: Technical Data

    t / s 1 0 0 0 1 0 0 k> 0,05 0,01 U/U> Fig. 6. Characteristic curve set B of overvoltage stage U>. Technical data Overvoltage stage U> Start voltage U> 0.8...1.6 x U Start time 0.1 s or 30 s Operate time at definite time mode of operation 0.05...1.00 s, 0.5...10.0 s or 5...100 s Time multiplier k>...
  • Page 35: Serial Communication Parameters

    The substation level control data communica- represented by the numbers 1, 2, 4...128. The Serial tor is able to read, over the SPA serial bus, the event mask is formed by multiplying above communication event data of the module, e.g. starting and numbers either by 0 (event not included in parameters tripping, from the over-/undervoltage relay...
  • Page 36 Data to be In addition to the event code data transfer, the module over the serial communication bus. transferred over input data (I data), output data (O data), set- Further, part of the data can be changed over the serial bus ting values (S), memorized data (V data) and the SPA bus by separate commands.
  • Page 37 Data Code Data Values direct. Remotely set start value for stage U> 0.8...1.6 x U Remotely set operate time or time 0.05...100 s or multiplier for stage U> 0.05...1.00 Remotely set start value for stage U< 0.4...1.2 x U Remotely set operate time for stage U< 1...120 s Remotely set checksum of 0...255...
  • Page 38 Data Code Data Values direct. Type designation of the relay module SPCU 3C14 Reading of event register Time, channel number and event code Re-reading of event register Time, channel number and event code Reading of module status data 0 = normal state 1 = module been subject to automatic reset 2 = overflow of event register...
  • Page 39 Once the self-supervision system has detected a a red digit one (1) and a green code number Fault codes permanent relay fault, the IRF LED on the front that indicates the fault type. The fault code panel of the module is lit, and at the same time should be recorded and stated when service is the normally operated signal relay of the self- ordered.
  • Page 41 General characteristics of C-type relay modules User´s manual and Technical description > >> Self-supervision alarm indicator Indicators for measured values (Internal Relay Fault) Display, 1 + 3 digits STEP > Setting knob 1 STEP with indicator Step push-button (STEP) Stage 1 >...
  • Page 42 1MRS 750328-MUM EN General characteristics of Issued 96-02-19 C-type relay modules Version A (replaces 34 SPC 2 EN1) Checked L-W U Approved TK Data subject to change without notice Push-buttons ........................2 Contents Programming switches SG1 .................... 2 Setting knobs ........................3 Display ...........................
  • Page 43: Setting Knobs

    Most of the operating values and operating In addition to the settings made with the setting Setting knobs times are set by means of the setting knobs on knobs, most modules allow so called remote the front panel of the relay module. Each setting setting.
  • Page 44: Display Submenu

    Display submenu Less important values and values not very often display moves forward when pressing the STEP set are displayed in the submenus. The number button for one second and backward when of submenus varies with different relay module pressing it for 0.5 seconds. The return to the types.
  • Page 45 Example 1: Function in the setting mode. Manual setting of the address code of a relay module and the data Set the digit by means of the STEP button. transfer rate for the serial communication. The initial value for the address code is 146. Press push-button STEP until register address A appears on the display.
  • Page 46: Stored Information

    Stored information The parameter values measured at the moment Register A contains the address code of the relay when a fault occurs are recorded in the registers, module as required by the serial communication in some modules also the setting values. The system.
  • Page 47: Trip-Test Mode

    Trip-test mode Register 0 also allows access to the so called The selected starting or tripping is activated by Trip-test function, which allows the output simultaneous pressing of the push-buttons STEP signals of the relay module to be activated one by and RESET.
  • Page 48 Example 2: Trip-test function. Forced activation of the out- puts is made as follows: Press the RESET button for about 1 second until the indicator of the second setting knob starts flashing. Step forward on the display to register 0. Press the push-buttons RESET and STEP si- multaneously to activate tripping of stage 1 (e.g.
  • Page 49 A measuring relay module is provided with two The operation indicator starts glowing yellow Operation separate operating stages, each of which with its when the operating stage starts and red when a indicators own yellow/red operation indicator on the lower delayed tripping operates.
  • Page 52 ABB Oy Substation Automation P.O.Box 699 FIN-65101 VAASA Finland Tel. +358 (0)10 22 11 Fax.+358 (0)10 22 41094 www.abb.com/substationautomation...