Table 5.6.2
Alarm and Trip information
Bit
Name
b0
AX (ACB ON/OFF)
b1
Reserve
b2
PAL2 P.U. Alarm
b3
PAL2 OUT Alarm
b4
PAL1 P.U. Alarm
b5
PAL1 OUT Alarm
b6
OVER Alarm
b7
LTD Trip
b8
STD Trip
b9
INST Trip
b10
EPAL Alarm
b11
GFR(ER) Trip(Alarm)
b12
UVT Trip
b13
Reserve
b14
TAL Alarm
b15
Reserve
Table 5.6.4 Contact input
Bit
Name
b0
Input 1 *1
b1
Input 2 *1
b2
Input 3 *1
b3
Reserve
b4
Reserve
b5
Reserve
b6
Reserve
b7
Reserve
b8
b9
Position of ACB *1*2
b10
b11
Reserve
b12
Reserve
b13
Reserve
b14
Reserve
b15
Reserve
*1 BIF-CON is needed.
*2 BIF-CL is needed.
Table 5.6.6 Characteristic bit data
Bit
Name
b0
Tg (Te) Alarm or Trip
2
b1
I
t of STD
b2
MCR or INST
b3
I
2
t of PAL2 (AP)
b4
Reserve
b5
Reserve
b6
Reserve
b7
Position
b8
Reserve
b9
Reserve
b10
Reserve
b11
Reserve
b12
Reserve
b13
Reserve
b14
Reserve
b15
Reserve
Table 5.6.3 Reset memory
0
1
OFF
ON
Non
Alarm
Non
Alarm
Non
Alarm
Non
Alarm
Non
Alarm
Non
Trip
Non
Trip
Non
Trip
Non
Alarm
Non
Trip(Alarm)
Non
Trip
Non
Alarm
*1 "All items (b1)" is to reset all items of b0, b2, b7 and b14.
Table 5.6.5 Contact output
0
1
OFF
ON
OFF
ON
OFF
ON
Disconnected
Connected
Test
Table 5.6.7 ETR Self diagnosis
0
1
Alarm
Trip
A/D converter Err.
OFF
ON
EEPROM Err.
INST
MCR
Date and Time IC (RTC) Err.
OFF(Flat)
ON (I
2
t)
Main setting module Err.
Option setting module Err.
CT Connector Err.
MCR switch Err.
TAL sensor Err.
*Some error mode may not be detected.
E-22
Bit
Name
b0
Alarm and Trip info.
b1
All items
b2
All max. and min. measurement
b3
Reserve
b4
Reserve
b5
Reserve
b6
Reserve
b7
Alarm and trip history
b8
Reserve
b9
Reserve
b10
Reserve
b11
Reserve
b12
Reserve
b13
Reserve
b14
Wh and varh
b15
Reserve
Bit
Name
b0
SHT ON (ACB OFF) *1
b1
CC ON (ACB ON) *1
b2
MD ON (Charge Spring) *1
b3
Reserve
b4
Reserve
b5
Reserve
b6
Reserve
b7
Reserve
b8
Reserve
b9
Reserve
b10
Reserve
b11
Reserve
b12
Reserve
b13
Reserve
b14
Reserve
b15
Reserve
*1 BIF-CON is needed.
ETR Err. Type
0
1
No reset
Reset
No reset
Reset
No reset
Reset
No reset
Reset
No reset
Reset
0
1
OFF
ON
OFF
ON
OFF
ON
Err. code
11H
12H
13H
21H
22H
23H
24H
25H

Advertisement