Mitsubishi Electric AE630-SW Instruction Manual page 9

Low-voltage air circuit breakers type ae, modbus interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

●(C) Terminals
1)
Name
Description
P1, P2
100-240V AC・DC
FG
Frame ground
T/R+
RS-485 signal +
T/R-
RS-485 signal -
COM
RS-485 signal GND
SLD
Modbus cable shield
Ter.
Terminator
■1): Terminal assignment is shown in
■2): These terminals should be connected with wire using crimp-type terminal.
The available crimp-type terminal is shown in figure 3.5.
BIF-MD
BIF-MD
Independent ground...Best
Fig 3.4: Short wire in case of ends of network
2)
Screw
(Tighten torque)
Fuse or Circuit Breaker shall be installed in power supply line.
Do not connect to main circuit of breaker directly.
1. This terminal has to be grounded to the protective ground
conductor by a thick wire of low impedance (*ground
resistance: 100 ohm or less).
2. Connect the FG terminal of each BIF-MD independently. If
not use ground independently, use common ground according
M3
to the figure 3.3.
(0.5 to 0.6N.m)
For Modbus cable.
In case of two wires cable, no need to use.
There is a terminate register in this device.
In case of the ends of network, connect two Ter. terminals by
short wire as shown in figure 3.4.
"6. Outline dimensions"
.
BIF-MD
BIF-MD
Common ground...Good
Fig 3.3: Ground connection
E-9
Notes
BIF-MD
BIF-MD
Common ground...NG
max. 6mm
Fig 3.5: Crimp-type terminal