Mitsubishi Electric AE630-SW Instruction Manual page 29

Low-voltage air circuit breakers type ae, modbus interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

Table 5.6.15 Energy register
Address
Number
Access
of bytes
Dec.
Hex.
1280
0500h
2
1281
0501h
2
1282
0502h
2
1283
0503h
2
1284
0504h
2
1285
0505h
2
1286
0506h
2
1287
0507h
2
1288
0508h
2
1289
0509h
2
1290
050Ah
2
1291
050Bh
2
1292
050Ch
2
1293
050Dh
2
1294
050Eh
2
1295
050Fh
2
1296
0510h
2
1297
0511h
2
1298
0512h
2
1299
0513h
2
1300
0514h
2
1301
0515h
2
1302
0516h
2
1303
0517h
2
1304
0518h
4
1306
051Ah
4
1308
051Ch
4
1310
051Eh
4
1312
0520h
4
*All above data can not be monitored without VT unit.
*The active and reactive energy are stored in the EEPROM of Extension module (EX1) when the power supply form Power supply
module (P1-P5) is cut off.
*1 Addresses 0518h-0520h can be accessed only from the even number address.
If the byte count of start address 0518h and 051Ah etc. is 2, 3, 5, or 6-byte, the error code (illegal data address code :02h) is
returned.
<Example> In case of monitoring active energy (0518H).
Slave address :01H
Query framing
01H
03H
Slave
Function
address
Code
Response framing
01H
03H
Slave
Function
Address
Code
Register Name
R
Active energy
R
R
Reserved
R
Reserved
R
Reactive energy (Lag)
R
R
Reserved
R
Reserved
R
Reactive energy (Lead)
R
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Reserved
R
Active energy (4 bytes) *1
R
Reserved
R
Reactive energy (4 bytes) *1
R
Reserved
R
Reactive energy (4 bytes) *1
05H
18H
Starting address
04H
HH
HL
Byte count
Active energy
E-29
Unit
kWh
MWh
kvarh
Mvarh
kvarh
Mvarh
kWh
kvarh
kvarh
00H
02H
quantity of registers
LH
LL
Lo
Hi
CRC
Range
0 to 999
0 to 999
0 to 999
0 to 999
0 to 999
0 to 999
0 to 99999999
0 to 99999999
0 to 99999999
Lo
Hi
CRC