6.3 Connection of Remote I/O Power

+24 VDC is required to run the remote I/O unit. Prepare a stabilized power supply that satisfies the
following conditions.
Output voltage
Max. output
current
The +24VDC power for the control circuit is supplied from the connector DCIN on the bottom of the unit.
When manufacturing the R300 cable, use the single-end connector CN300 (optional, with one end), and
when manufacturing the R301 cable, use the connector set CS301 (optional, with two ends).
24VDC(+ )
0V
FG
Stabilized power supply
(Prepare separately)
CAUTION
Do not apply voltages other than those indicated in this manual on the connector. Doing
so may lead to destruction or damage.
Incorrect connections could damage the device, so always connect the cable to the
designated connector.
CHAPTER 6 CONNECTION OF REMOTE I/O UNIT
6.3 Connection of Remote I/O Power
Ripple
FCUA-DX10
FCUA-DX11
FCUA-DX12
FCUA-DX13
FCUA-DX14
R220 cable
+24V±5%
±5% (P-P)
2.4A or more
3.8A or more
3.8A or more
3.4A or more
3.4A or more
(Fr on t)
( Rear )
75
DCIN
Bottom
1
+24VDC
2
0V
FG
3