Pulse / Alarm; Pulse Output - Beko METPOINT FLM SF53 Installation And Operation Instruction Manual

Thermal flow meter
Hide thumbs Also See for METPOINT FLM SF53:
Table of Contents

Advertisement

EN

6.5. Pulse / alarm

Setup → Pulse/Alarm
The galvanically isolated pulse output can be used as a pulse or as an alarm output.

6.5.1. Pulse output

The maximum permissible number of pulses per second is 50. Pulse output is delayed by 1 second.
Pulse factor
0.02642 gal / pulse
0.2642/ pulse
3.5315 ft³ / pulse
635,664.00
35,3147 ft³ / pulse
6,356,640.01
Table 1: Maximum flow volumes for pulse output
NOTICE
Important information
Entering pulse valences that do not allow the measurement range end value to be displayed is not
allowed. Such entries are discarded and an error message is displayed.
METPOINT
SF53
®
The following units can be selected for the alarm output:
kg/min, cfm, l/s, m³/h, m/s, °F, °C, kg/s
° F
Press "Value" to enter the alarm value. Press "Hyst". to enter the desired
hysteresis.
Hi-Lim: upper limit
Lo-Lim: lower limit
The following units can be selected for pulse output:
l
kg, cd, l, m³
Select "Value" to enter the pulse factor (0.1, 1, 10, 100). Select "Polarity" to enter
the switching state (plus = 0 → 1, minus = 1 → 0).
[ft³/h]
[ft³/min]
635.67
10.59
6,356.64
105.94
10,594.40
105,944.00
[gal/min]
79.25
792.52
79,251.62
792,516.16